PHOENIX CONTACT IB IL AO 2/UI-XC-PAC IB IL AO 2/UI-XC-PAC 2701389 PHOENIX CONTACT Inline terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IB IL AO 2/UI-XC-PAC 2701389 PHOENIX CONTACT Inline terminal

IB IL AO 2/UI-XC-PAC

2701389

PHOENIX CONTACT

1 Pcs.

Inline terminal Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA... 20 mA, 4 mA... 20 mA, -20 mA... 20 mA, connection technology: 2 conductors, transmission rate on the local bus: 500 kBit/s, Extreme Conditions variant, protection rating: IP20, including inline connector and marking surface Inline, Analog output terminal, Analog outputs: 2, 0 V ... 10 V, -10 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA, -20 mA ... 20 mA, connection technology: 2-conductor, transmission speed in the local bus: 500 kbps, Extreme conditions version, degree of protection: IP20, including Inline connector and labeling field

Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An Inline terminal is utilized in modular automation setups to expand controller capabilities, handle peripheral signals, and communicate across local bus networks.

This Phoenix Contact IB IL AO 2/UI-XC-PAC part integrates seamlessly into industrial control architectures requiring reliable signal processing. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Width: 12.2 mm
  • Height: 119.8 mm
  • Depth: 71.5 mm
  • Note on dimensions: Housing dimensions
  • Note on application Note on application: Only for industrial use
  • Inline local bus Number of interfaces: 2
  • Connection method: Inline data jumper
  • Transmission speed: 500 kbps
  • Transmission physics: Copper
  • Module ID code (dec.): 91
  • ID code (hex): 5B
  • Length code (hex): 04
  • Length code (dec): 4
  • Process data channel: 64 bit
  • Input address area: 8 Byte
  • Output address area: 8 Byte

More info

▲
Technical data

Dimensions
Dimensional drawing
Width12.2 mm
Height119.8 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Notes
Note on application
Note on applicationOnly for industrial use

Interfaces
Inline local bus
Number of interfaces2
Connection methodInline data jumper
Transmission speed500 kbps
Transmission physicsCopper

System properties
Module
ID code (dec.)91
ID code (hex)5B
Length code (hex)04
Length code (dec)04
Process data channel64 bit
Input address area8 Byte
Output address area8 Byte
Register length64 bit
Required parameter data10 Byte
Required configuration data5 Byte

Output data
Analog:
Output nameAnalog outputs
Connection technology2-conductor
Note regarding the connection technologyshielded
Number of outputs2
D/A conversion timetyp. 10 µs
D/A converter resolution12 bit
Protective circuitShort-circuit and overload protection; Electronic
Transient protection; Suppressor diode
Data formatsIB IL, S7-compatible
Representation of output values12 bits (11 bits + sign bit)
Process data updatebus-synchronous
Current output signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Load/output load current output≤ 450 Ω
Voltage output signal0 V ... 10 V
-10 V ... 10 V
Load/output load voltage output> 1 kΩ
Permissible cable lengthmax. 250 m (The specifications refer to nominal operation after complying with installation instructions. The specifications refer to the following reference cable type: Shielded power station cable: LiYCY; 2 x 2 x 0,5 mm²; VDE0812)

Product properties
Product typeI/O component
Product familyInline
Typemodular
Scope of deliveryincluding Inline connector and labeling field
Special propertiesExtreme conditions version
Diagnostics messagesFailure of the internal I/O supply I/O error message sent to the bus coupler
I/O supply failure Message in the diagnostic code (in the IB IL format)
Short circuit/overload of the outputs Message in the diagnostic code (in the IB IL format)
Configuration invalid Message in the diagnostic code (in the IB IL format)
Data management status
Article revision03
Insulation characteristics
Overvoltage categoryII (IEC 60664-1, EN 60664-1)
Pollution degree2 (IEC 60664-1, EN 60664-1)

Electrical properties
Potentials: Communications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current drawmax. 65 mA
typ. 55 mA
Potentials: Supply of analog modules (UANA)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current drawmax. 75 mA (Nominal current load (IOUT1/2= 20 mA, RL= 0 Ω))
max. 30 mA (No-load)
typ. 38 mA (Nominal voltage load (UOUT1/2= 10 V, RL= 1 kΩ))
max. 45 mA (Nominal voltage load (UOUT1/2= 10 V, RL= 1 kΩ))
typ. 65 mA (Nominal current load (IOUT1/2= 20 mA, RL= 0 Ω))
typ. 24 mA (No-load)
Electrical isolation/isolation of the voltage ranges
Test voltage: 7.5 V supply (bus logics)/24 V analog supply (analog I/O)500 V AC, 50 Hz, 1 min.
Test voltage: 7.5 V supply (bus logic)/functional ground500 V AC, 50 Hz, 1 min.
Test voltage: 24 V analog supply (analog I/O)/functional ground500 V AC, 50 Hz, 1 min.

Connection data
Connection technology
Connection nameInline connector
Conductor connection
Connection methodSpring-cage connection
Conductor cross section rigid0.08 mm² ... 1.5 mm²
Conductor cross section flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm
Inline connector
Connection methodSpring-cage connection
Conductor cross section, rigid0.08 mm² ... 1.5 mm²
Conductor cross section, flexible0.08 mm² ... 1.5 mm²
Conductor cross section AWG28 ... 16
Stripping length8 mm

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Degree of protectionIP20
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)10 % ... 95 % (non-condensing)

Standards and regulations
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)

Mounting
Mounting typeDIN rail mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.