PHOENIX CONTACT IB IL AI 4/EF-XC-PAC IB IL AI 4/EF-XC-PAC 2701215 PHOENIX CONTACT Inline terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

IB IL AI 4/EF-XC-PAC 2701215 PHOENIX CONTACT Inline terminal

IB IL AI 4/EF-XC-PAC

2701215

PHOENIX CONTACT

1 Pcs.

Inline terminal Inline, Analog Input Module, Analog Inputs: 4, 0 V ... 5 V, -5 V ... 5 V, 0 V ... 10 V, -10 V ... 10 V, 0 mA... 20 mA, 4 mA... 20 mA, -20 mA... 20 mA, connection technology: 2, 3, 4 conductors, transmission rate on the local bus: 500 kBit/s, Extreme Conditions variant, protection rating: IP20, including inline connectors and marking fields

Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Consolidating field measurements into a modular automation network is the primary role of an Inline terminal designed for process monitoring. This Phoenix Contact part number IB IL AI 4/EF-XC-PAC offers reliable signal conditioning and conversion for multi-channel analog inputs in industrial setups. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Supply voltage DC (EF007534): 19.2 V
  • Voltage type (supply voltage) (EF002991): DC
  • Input, current (EF003204): Yes
  • Input, voltage (EF003205): Yes
  • Input, resistor (EF003206): No
  • Input, resistance thermometer (EF003207): No
  • Input, thermocouple (EF003208): No
  • Input signal, configurable (EF003209): Yes
  • Resolution of the analogue inputs (EF003575): 16 Bit
  • Output, current (EF003212): No
  • Output, voltage (EF003213): No
  • Output signal configurable (EF003214): No
  • Number of analogue inputs (EF001994): 4
  • Number of analogue outputs (EF001995): 0
  • Analogue inputs configurable (EF008518): Yes
  • Analogue outputs configurable (EF008519): No

More info

▲

Key Commercial Data

Orderkey2701215
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 160 (C-6-2017)
GTIN4046356727839
Weight per Piece (excluding packing)210.000 g
Custom tariff number85389091
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Dimensional drawing
Width48.8 mm
Height135 mm
Depth71.5 mm
Note on dimensionsHousing dimensions

Ambient conditions

Ambient temperature (operation)-25 °C ... 55 °C (Standard)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Permissible humidity (operation)10 % ... 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport)10 % ... 95 % (according to DIN EN 61131-2)
Air pressure (operation)70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protectionIP20

General

Mounting typeDIN rail
Net weight210 g
Note on weight specificationswith connectors
Operating modeProcess data mode with 5 words/1 word PCP

Interfaces

DesignationInline local bus
Connection methodInline data jumper
Transmission speed500 kbps
Transmission physicsCopper

Inline potentials

DesignationCommunications power (UL)
Supply voltage7.5 V DC (via voltage jumper)
Current consumptiontyp. 85 mA
max. 100 mA
DesignationSupply of analog modules (UANA)
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumptiontyp. 13 mA
max. 20 mA
DesignationMain circuit supply (UM)
Supply voltage24 V DC (via voltage jumper)
Supply voltage range19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption0 A
max. 200 mA

Analog inputs

Description of the inputDifferential input, including sensor supply (24 V DC)
Input nameAnalog inputs
Number of inputs4
Connection methodInline shield connector
Connection technology2, 3, 4-wire
Note regarding the connection technologyshielded
A/D conversion timemax. 10 µs
Resolution A/D16 bit
Limit frequency (3 dB)500 Hz
Type of protectionTransient protection
Overload protection
Data formatsIB IL, IB ST, standardized representation, S7 compatible
Measured value resolution16 bits (15 bits + sign bit)
Current input signal0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
Input resistance current inputapprox. 110 Ω
Voltage input signal0 V ... 5 V
-5 V ... 5 V
0 V ... 10 V
-10 V ... 10 V
Input resistance of voltage input300 kΩ

Electrical isolation

Test section5 V supply, incoming remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min.
5 V supply, outgoing remote bus/7.5 V supply (bus logics) 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min.
7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min.
I/O / functional earth ground 500 V AC 50 Hz 1 min.

Standards and Regulations

Connection in acc. with standardCUL
Protection classIII, IEC 61140, EN 61140, VDE 0140-1

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.