View larger
IB IL TEMP 4/8 RTD-PAC 2863915 PHOENIX CONTACT Inline function terminal
IB IL TEMP 4/8 RTD-PAC
2863915
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Inline function terminal type IB IL TEMP 4/8 RTD-PAC from Phoenix Contact (model IB IL TEMP 4/8 RTD-PAC 2863915 PHOENIX CONTACT Inline function terminal) serves as a specialized I/O component used to interface temperature sensors like resistance thermometers directly with a modular automation station. Such terminals condition sensor signals for accurate thermal monitoring in complex manufacturing processes.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): Yes
- Input, resistance thermometer (EF003207): Yes
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): No
- Number of HW-interfaces industrial Ethernet (EF003020): 0
More info
▲Key Commercial Data
| Orderkey | 2863915 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 165 (C-6-2017) |
| GTIN | 4017918955410 |
| Weight per Piece (excluding packing) | 190.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
Interfaces
| Designation | Inline local bus |
|---|---|
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Transmission physics | Copper |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 75 mA |
| max. 100 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 28 mA |
| max. 55 mA | |
| Power consumption | typ. 1.24 W |
Analog inputs
| Number of inputs | 8 |
|---|---|
| Input name | Analog RTD inputs |
| Description of the input | Input for resistive temperature sensors |
| Connection method | Spring-cage connection |
| Connection technology | 2, 3-conductor |
| Sensor types (RTD) that can be used | Pt, Ni, KTY, Cu sensors, linear resistors |
| Linear resistance measuring range | 0 Ω ... 400 Ω |
| 0 Ω ... 20 kΩ | |
| Measuring principle | Successive approximation |
| Measured value representation | 16 bits (15 bits + sign bit) |
| A/D conversion time | max. 10 µs |
| Process data update | 6 ms (Up to 230 ms possible depending on operating mode) |
| Data formats | IB IL, IB ST, S7 compatible |
Electrical isolation
| Test section | 7.5 V supply (bus logic)/±15.5 V, ±5 V analog supply (analog I/O) 500 V AC 50 Hz 1 min. |
|---|---|
| 7.5 V supply (bus logics) / functional earth ground 500 V AC 50 Hz 1 min. | |
| ±15.5 V, ±5 V analog supply (analog I/O)/functional earth ground 500 V AC 50 Hz 1 min. |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |