View larger
IB IL AI 2-HART-PAC 2862149 PHOENIX CONTACT Inline terminal
IB IL AI 2-HART-PAC
2862149
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact inline terminal IB IL AI 2-HART-PAC acts as a HART-capable analog input module designed to integrate intelligent field devices into modular control stations. These units process standard current loops while supporting digital communication parameters for advanced device diagnostics and configuration.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): Yes
- Input, voltage (EF003205): No
- Input, resistor (EF003206): No
- Input, resistance thermometer (EF003207): No
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): Yes
- Resolution of the analogue inputs (EF003575): 16 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 2
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): Yes
- Analogue outputs configurable (EF008519): No
More info
▲Key Commercial Data
| Orderkey | 2862149 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 161 (C-6-2017) |
| GTIN | 4017918918835 |
| Weight per Piece (excluding packing) | 134.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 134 g |
| Operating mode | Process data operation with 2 words, PCP with 2 words |
| Diagnostics messages | Failure of the internal I/O supply Yes |
| Peripheral fault Error message in the process data | |
| User error Error message in the process data |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
| Transmission physics | Copper |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 95 mA |
| max. 110 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 50 mA |
| max. 150 mA | |
| Power consumption | typ. 1.9 W |
Analog inputs
| Description of the input | Differential inputs, current |
|---|---|
| Input name | Analog inputs |
| Number of inputs | 2 |
| Connection method | Inline shield connector |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded |
| A/D conversion time | approx. 10 µs (bus-synchronous) |
| Resolution A/D | 16 bit |
| Limit frequency (3 dB) | 25 Hz |
| Type of protection | Surge protection |
| Data formats | IB IL, standardized representation, PIO |
| Measuring principle | Successive approximation |
| Measured value resolution | 16 bits (15 bits + sign bit) |
| Measured value representation | 16 bit two's complement |
| Current input signal | 4 mA ... 20 mA |
| 0 mA ... 25 mA | |
| Input resistance current input | 250 Ω |
| Common mode voltage range signal - ground | 40 V (between current input and functional earth ground) |
Electrical isolation
| Test section | 7.5 V supply (bus logic), 24 V supply UANA/ I/O 500 V AC 50 Hz 1 min. |
|---|---|
| 7.5 V supply (bus logic), 24 V supply UANA/functional earth ground 500 V AC 50 Hz 1 min. | |
| I/O / functional earth ground 500 V AC 50 Hz 1 min. |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Protection class | III, IEC 61140, EN 61140, VDE 0140-1 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |