PHOENIX CONTACT PSR-MC32-3NO-1NC-24-230UC-SP PSR-MC32-3NO-1NC-24-230UC-SP 2700525 PHOENIX CONTACT Safety relays View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-MC32-3NO-1NC-24-230UC-SP 2700525 PHOENIX CONTACT Safety relays

PSR-MC32-3NO-1NC-24-230UC-SP

2700525

PHOENIX CONTACT

1 Pcs.

Safety relays Safety relay for emergency stop, safety doors and light curtains up to SIL 3, cat. 4, PL e, 1 or 2 channel service, automatic or manual controlled start, 3 trip circuits, 1 signaling circuit, US = 24 ... 230 V AC/DC, plug-in push-in terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact PSR-MC32-3NO-1NC-24-230UC-SP is a safety relay applied in industrial control architectures to manage emergency stop loops and protective door monitors. These modules provide galvanic isolation and safe switching behavior for automated production lines. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Model (EF000010): Basic device
  • Suitable for rail mounting (EF003972): Yes
  • With detachable clamps (EF003340): Yes
  • Type of electric connection (EF003961): Spring clamp connection
  • Suitable for monitoring of position switches (EF007270): Yes
  • Suitable for monitoring of valves (EF007272): No
  • Suitable for monitoring of tactile sensors (EF007271): No
  • Suitable for monitoring of magnetic switches (EF007266): Yes
  • Suitable for monitoring of proximity switches (EF007267): No
  • With start input (EF003342): No
  • With muting function (EF004057): No
  • With feedback circuit (EF003343): Yes
  • Release-delay (EF001129): 0.15 s
  • With approval for BG BIA (EF004145): No
  • With approval according to UL (EF001783): No
  • Width (EF000008): 22.5 mm

More info

▲

Key Commercial Data

Orderkey2700525
Packing unit1 pc
Catalog pagePage 253 (C-6-2017)
GTIN4046356912709
Weight per Piece (excluding packing)235.400 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restriction1

Dimensions

Width22.5 mm
Height117.4 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 55 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 85 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Power supply

Rated control circuit supply voltage US24 V AC/DC ... 230 V AC/DC -15 % / +10 %
Rated control supply current IStyp. 103 mA (24 V DC)
typ. 47 mA (48 V DC)
typ. 38 mA (110 V AC)
typ. 21 mA (230 V AC)
Power consumption at US2.7 W (with DC)
2.9 W (with AC)
Apparent powertyp. 5 VA (at US)
Inrush current< 80 A (Δt = 50 µs at Us)
Filter time2 ms (at A1 in the event of voltage dips at Us)
Protective circuitUS: surge protection 275 V varistor / 411 V suppressor diode

Digital inputs

Input voltage range "0" signal0 V DC ... 5 V DC (for safe Off; at S10/S12/S13)
Input current range "0" signal0 mA ... 2 mA (for safe Off; at S10/S12/S13)
Inrush current< 5 mA (with Us/Ixat S10/S12/S13)
> -5 mA (with Us/Ixto S22)
< 10 mA (with Us/Ixat S34/S35)
Current consumption< 5 mA (at Us/Ixto S10/S12/S13/S34/S35)
> -5 mA (with Us/Ixto S22)
Filter timemax. 1.5 ms (to S10-S12; test pulse width; at 24 V DC)
7.5 ms (to S10-S12; test pulse rate; at 24 V DC)
Test pulse rate = 5 x Test pulse width
Voltage at input/start and feedback circuit24 V DC -20 % / +25 %
Max. permissible overall conductor resistance150 Ω
Concurrence input 1/2∞
Type of protectionInputs: protection against polarity reversal, surge protection
Protective circuit/component38.6 V suppressor diode

Relay outputs: enabling current path

Output nameEnabling current path
Output descriptionsafety-related N/O contacts
Number of outputs3 (undelayed)
Contact type3 enabling current paths
Contact materialAgSnO2
Switching voltagemin. 5 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Limiting continuous current6 A (observe derating)
Inrush currentmin. 10 mA
max. 6 A
Sq. Total current72 A2(observe derating)
Switching capacitymin. 50 mW
Switching frequencymax. 1 Hz
Interrupting rating (ohmic load) max.1500 VA (250 V AC, τ = 0 ms)
For additional values, see load curve
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
36 W (60 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
33 W (220 V DC, τ = 40 ms)
1500 VA (250 V AC, τ = 40 ms)
Mechanical service life10x 106cycles
Switching capacity according to IEC 60947-5-15 A (24 V (DC13))
5 A (250 V (AC15))
Output fuse6 A gL/gG
4 A gL/gG (for low-demand applications)

Relay outputs: return current/signaling current path

Output nameSignaling current path
Output descriptionnon-safety-related N/C contact
Number of outputs1 (undelayed)
Contact type1 signaling current path
Contact materialAgSnO2
Switching voltagemin. 5 V AC/DC
max. 250 V AC/DC
Limiting continuous current6 A
Inrush currentmin. 10 mA
max. 6 A
Switching capacitymin. 50 mW
Switching frequency1 Hz
Mechanical service life10x 106cycles
Output fuse6 A gL/gG
4 A gL/gG (for low-demand applications)

Times

Typical pickup time at US< 200 ms (when controlled via A1)
Typical response time at US< 150 ms (automatic start)
< 100 ms (manual, monitored start)
Typical release time at US< 20 ms (when actuation is via the sensor circuit)
Restart time< 1 s
Recovery time< 500 ms

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight235.4 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow
Operating voltage display1 x green LED
Status display3 x green LED

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3
DesignationEN ISO 13849
Performance level (PL)e
Category4 (5 A DC13; 5 A AC15; 8760 switching cycles/year)
Safety Integrity Level Claim Limit (SIL CL)3

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178; EN 60947-5-1
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV between enabling current path (23/24) and enabling current path (33/34) and signaling current path (41/42)
Basic insulation 4 kV between all current paths and housing
Safe isolation, reinforced insulation 6 kV between all other circuits
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant

Environmental Product Compliance

REACh SVHCLead 7439-92-1
China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.