IB IL RTD 4/PT100-ECO 2702499 PHOENIX CONTACT Inline terminal
IB IL RTD 4/PT100-ECO
2702499
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - analogue I/O module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact IB IL RTD 4/PT100-ECO inline terminal is an input module engineered to process resistance temperature detector signals within modular control station setups. These terminals provide reliable thermal measurement processing for factory automation and machinery protection schemes.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Supply voltage DC (EF007534): 19.2 V
- Voltage type (supply voltage) (EF002991): DC
- Input, current (EF003204): No
- Input, voltage (EF003205): No
- Input, resistor (EF003206): Yes
- Input, resistance thermometer (EF003207): Yes
- Input, thermocouple (EF003208): No
- Input signal, configurable (EF003209): No
- Resolution of the analogue inputs (EF003575): 24 Bit
- Output, current (EF003212): No
- Output, voltage (EF003213): No
- Output signal configurable (EF003214): No
- Number of analogue inputs (EF001994): 0
- Number of analogue outputs (EF001995): 0
- Analogue inputs configurable (EF008518): No
- Analogue outputs configurable (EF008519): No
More info
▲Key Commercial Data
| Orderkey | 2702499 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 143 (C-6-2017) |
| GTIN | 4055626203195 |
| Weight per Piece (excluding packing) | 69.000 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | 0 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 69 g |
| Note on weight specifications | with connector |
| Diagnostics messages | Failure of the internal I/O supply I/O error message sent to the bus coupler |
| Checksum error I/O error message sent to the bus coupler |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | typ. 56 mA |
| max. 85 mA | |
| Designation | Supply of analog modules (UANA) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current consumption | typ. 7.3 mA |
| max. 14 mA | |
| Power consumption | typ. 0.67 W |
Analog inputs
| Number of inputs | 4 (Pt 100) |
|---|---|
| Input name | Analog RTD inputs |
| Description of the input | Inputs for resistive temperature sensors |
| Connection method | Inline connector |
| Connection technology | 2-wire |
| Note regarding the connection technology | shielded |
| Sensor types (RTD) that can be used | Pt 100 (IEC 60751/EN 60751) |
| Nominal value of the current sources | 1 mA (pulsed current, the data is valid during the sampling phase) |
| A/D conversion time | typ. 120 ms |
| Resolution A/D | 24 bit |
| Process data update | < 10 ms |
| Type of protection | Overload protection |
| Transient protection | |
| Data formats | Standardized representation |
| Input filter time | 120 ms (per channel) |
| Input filter | Digital filter |
Electrical isolation
| Test section | Bus logic (local bus, communications power) 500 V AC 50 Hz 1 min. |
|---|---|
| Analog I/O 500 V AC 50 Hz 1 min. | |
| Functional earth ground 500 V AC 50 Hz 1 min. |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
| No hazardous substances above threshold values |