The IB IL CNT-PAC/10 2897046 PHOENIX CONTACT Module counter compact serves as a modular input device designed to register high-frequency event pulses and measure operational cycles in industrial equipment. Compact counter units are frequently deployed in automated processing lines for batch counting, frequency measurement, and position tracking. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of functions (EF003244): 1
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for TCP/IP (EF003050): No
- Supporting protocol for PROFIBUS (EF003052): Yes
- Supporting protocol for CAN (EF003053): No
More info
▲Commercial data
| Order key | 2897046 |
|---|---|
| Packaging unit | 10 pcs |
| Sell key | DRI163 - |
| Minimum Order Quantity | 10 pcs |
| Ean | 4046356139021 |
| Weight per unit (excluding packaging) | 130,000 g |
| Tariff rate number | 85389091 |
| Country of origin | DE (Germany) |
Observation
| Restriction of Use | EMC: Class A product, see manufacturer's declaration in the download center |
|---|
Environmental conditions
| Ambient Temperature (Service) | -25°C ... 55 °C |
|---|---|
| Ambient Temperature (Storage/Transport) | -25 °C ... 85 °C |
| Permissible air humidity (service) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Permissible air humidity (storage/transport) | 10 % ... 95 % (according to DIN EN 61131-2) |
| Air Pressure (Service) | 70 kPa... 106 kPa (up to 3000 m above NN) |
| Air Pressure (Storage/Transport) | 70 kPa... 106 kPa (up to 3000 m above NN) |
| Protection Index | IP20 |
General
| Type of mounting | Rail |
|---|---|
| net weight | 130 g |
| Observation about weight indications | with connectors |
| Operating Mode | Process Data Service with Two Words |
| Diagnostic messages | Short circuit of sensor power |
| Overloading the sensor power supply |
Interfaces
| Denomination | Bus local Inline |
|---|---|
| Connection type | Inline data handling |
| Transmission speed | 500 kBit/s |
| Transmission Physics | copper |
Inline Potentials
| Denomination | Logic Supply (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via potential maneuver) |
| Current absorption | typ. 40 mA |
| max. 50 mA | |
| Power Consumption | max. 0.375 W (to UL) |
| Denomination | Segment Circuit Power (U)s) |
| Supply voltage | 24 V DC (via potential maneuver) |
| Current absorption | max. 1 A |
Counter Inputs
| Denomination Entry | Counter input for 24 V signals |
|---|---|
| Number of Entries | 1 (only one counter input can be used, either for 24 V or 5 V signals) |
| Connection type | Spring-loaded connection |
| Operating Mode | Event counting, frequency/time measurement |
| Input voltage | 24 V DC |
| 30 V DC (maximum) | |
| Input Voltage Range Signal "0" | 0 V DC ... 5 V DC |
| Input Voltage Range Signal "1" | 15 V DC ... 30 V DC |
| Input Frequency | max. 100 kHz |
| Input current | typ. 5 mA |
| Denomination Entry | Counter input for 5 V signals |
| Number of Entries | 1 (only one counter input can be used, either for 24 V or 5 V signals) |
| Connection type | Spring-loaded connection |
| Connection technology | 2 wires (shielded), 5V external power supply |
| Operating Mode | Event counting, frequency/time measurement |
| Input voltage | 5 V DC (Rated Voltage) |
| 8 V DC (maximum) | |
| Input Voltage Range Signal "0" | 0 V ... 1.5 V |
| Input Voltage Range Signal "1" | 3.5 V ... 8 V |
| Input Frequency | max. 100 kHz |
| Input current | typ. 5 mA |
| Input resistance | approx. 1.7 kΩ |
Digital outputs
| Denomination Output | Switching Output |
|---|---|
| Connection type | Spring-loaded connection |
| Connection technology | 2 conductors |
| Number of outputs | 1 |
| Name of protection | Short Circuit Protection |
| Overload protection | |
| Output voltage | 24 V DC (Rated Voltage) |
| Output current | max. 0.5 A (Rated Current) |
| Inductive Rated Load | max. 12 VA (1.2 H, 48 Ω) |
| Nominal lamp load | max. 12 W |
| Resistive Load Rating | max. 12 W (48 Ω) |
Standards & Specifications
| Kind of protection | III, IEC 61140, EN 61140, VDE 0140-1 |
|---|
Environmental Product Compliance
| China RoHS | Time slot for intended use: unlimited = EFUP-e |
|---|---|
| No hazardous substances above thresholds |
Classifications
eCl@ss
| eCl@ss 4.0 | 27250304 |
|---|---|
| eCl@ss 4.1 | 27250304 |
| eCl@ss 5.0 | 27250304 |
| eCl@ss 5.1 | 27242605 |
| eCl@ss 6.0 | 27242605 |
| eCl@ss 7.0 | 27242605 |
| eCl@ss 8.0 | 27242605 |
| eCl@ss 9.0 | 27242605 |
ETIM
| ETIM 2.0 | EC001433 |
|---|---|
| ETIM 3.0 | EC001601 |
| ETIM 4.0 | EC001601 |
| ETIM 5.0 | EC001601 |
| ETIM 6.0 | EC001601 |
UNSPSC
| UNSPSC 6.01 | 43172015 |
|---|---|
| UNSPSC 7.0901 | 43201404 |
| UNSPSC 11 | 43172015 |
| UNSPSC 12.01 | 43201404 |
| UNSPSC 13.2 | 43201404 |