A safety module, the Phoenix Contact IB IL 24 PSDI 16-PAC, monitors safety-related signals and ensures protective shutdown sequences in industrial machinery. Such devices safeguard plant personnel by evaluating emergency stops, light curtains, and safety interlocks within an integrated control architecture.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 48.8 mm
- Height: 141 mm
- Depth: 71.5 mm
- Note on dimensions: Housing dimensions
- Note on application Note on application: Only for industrial use
- Inline local bus No. of channels: 2
- Connection method: Inline data jumper
- Transmission speed: 500 kbps / 2 Mbps (can be switched)
- Module ID code (dec.): 163
- ID code (hex): A3
- Length code (hex): 04
- Length code (dec): 04
- Process data channel: 8 Byte
- Input address area: 8 Byte ((Operating mode: SafetyBridge))
- Output address area: 8 Byte ((Operating mode: SafetyBridge))
- Register length: 8 Byte
More info
▲| Dimensional drawing | |
| Width | 48.8 mm |
| Height | 141 mm |
| Depth | 71.5 mm |
| Note on dimensions | Housing dimensions |
| Note on application | |
| Note on application | Only for industrial use |
| Inline local bus | |
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps / 2 Mbps (can be switched) |
| Module | |
| ID code (dec.) | 163 |
| ID code (hex) | A3 |
| Length code (hex) | 04 |
| Length code (dec) | 04 |
| Process data channel | 8 Byte |
| Input address area | 8 Byte ((Operating mode: SafetyBridge)) |
| Output address area | 8 Byte ((Operating mode: SafetyBridge)) |
| Register length | 8 Byte |
| Required parameter data | 1 Byte ((Operating mode: SafetyBridge)) |
| Required configuration data | 5 Byte ((Operating mode: SafetyBridge)) |
| Digital: | |
| Input name | Digital inputs |
| Description of the input | IEC 61131-2 type 3 |
| Number of inputs | 8 (for 2-channel assignment) |
| 16 (for 1-channel assignment) | |
| Cable length | max. 500 m (200 m from the clock output to the safe input (total based on forward and return path)) |
| Connection method | Spring-cage connection |
| Connection technology | 2-, 3-conductor |
| Input voltage | 24 V DC (via clock outputs UT1 and UT2 or external supply) |
| Input voltage range | -3 V DC ... 30 V DC |
| Input voltage range "0" signal | -3 V DC ... 5 V DC |
| Input voltage range "1" signal | 11 V DC ... 30 V DC |
| Typical input current per channel | 2.7 mA (at 24 V) |
| Product type | I/O component |
| Product family | Inline |
| Application | Functional safety |
| Type | modular |
| Data management status | |
| Article revision | 06 |
| Maximum power dissipation for nominal condition | 14.5 W |
| Transmission medium | Copper |
| Potentials: Communications power (UL) | |
| Supply voltage | 7.5 V DC (see safety data) |
| Current draw | max. 190 mA |
| Potentials: Main circuit supply (UM) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | max. 415 mA |
| typ. 15 mA (plus current consumption of the inputs when supplied via the clock outputs, plus current consumption of the connected initiators when via through the clock outputs) | |
| Supply: Module electronics | |
| Supply voltage | 24 V DC (via voltage jumper) |
| Supply voltage range | 19.2 V DC ... 30 V DC |
| Connection technology | |
| Connection name | Inline connector |
| pluggable | yes |
| Conductor connection | |
| Connection method | Spring-cage connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Inline connector | |
| Connection method | Spring-cage connection |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Ambient conditions | |
| Ambient temperature (operation) | -25 °C ... 55 °C |
| Degree of protection | IP20 |
| Air pressure (operation) | 80 kPa ... 108 kPa (up to 2000 m above sea level) |
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
| Permissible humidity (operation) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
| Permissible humidity (storage/transport) | 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |