View larger
Images are for illustrative purposes only. Please refer to data sheet for details
HC-B 6-I-UT-F 1648128 PHOENIX CONTACT Contact insert
HC-B 6-I-UT-F
1648128
PHOENIX CONTACT
1 Pcs.
Contact insert
Contact insert, number of poles: 6+PE, size: B6, number of connections per pole: 1, Female, Screw connection, 500 V, 16 A, 0.5 mm² ... 2.5 mm², Application: Power
Contact insert, number of positions: 6+PE, size: B6, number of connections per position: 1, Socket, Screw connection, 500 V, 16 A, 0.5 mm2 ... 2.5 mm2, application: Power
Connectors > Contact insert for rectangular connectors
Industrial plug-in connectors/interfaces
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact contact insert HC-B 6-I-UT-F is an industrial plug connector component designed to manage power circuits securely within heavy-duty connector hoods and panel housings.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General: for flexible conductors with or without ferrules:
- General: Connectors may be operated only when there is no load/voltage.:
- Assembly note: To ensure correct use, installation in housing with IP54 protection or better is required:
- Product type: Contact insert with a fixed no. of positions:
- Series: HC-B:
- Application: Power:
- Type: B6:
- Number of positions: 6:
- Connection profile: 6+PE:
- Contact numbering: 1 - 6:
- Number of connections per position: 1:
- Contact material type: turned:
- Screwdriver blade: 0.5 x 3.5 mm:
- Data management status Article revision: 19:
- Insulation characteristics Overvoltage category: III:
- Degree of pollution: 3:
More info
▲Technical data
Notes
| General | for flexible conductors with or without ferrules |
| General | Connectors may be operated only when there is no load/voltage. |
Mounting
| Assembly note | To ensure correct use, installation in housing with IP54 protection or better is required |
Product properties
| Product type | Contact insert with a fixed no. of positions |
| Series | HC-B |
| Application | Power |
| Type | B6 |
| Number of positions | 6 |
| Connection profile | 6+PE |
| Contact numbering | 1 - 6 |
| Number of connections per position | 1 |
| Contact material type | turned |
| Screwdriver blade | 0.5 x 3.5 mm |
| Data management status | |
| Article revision | 19 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
Dimensions
| Dimensional drawing | |
| Width | 34 mm |
| Height | 34.6 mm |
| Length | 50.5 mm |
| Drill hole distance, horizontal | 44 mm |
| Drill hole distance, vertical | 27 mm |
| Mechanical characteristics | |
| Contact diameter | 2.5 mm |
Connection data
| Connection technology | |
| Connection technology | Screw connection |
| Number of connections per position | 1 |
| Connection in acc. with standard | IEC / EN |
| Conductor connection | |
| Conductor cross section | 0.5 mm² ... 2.5 mm² |
| Connection cross section AWG | 20 ... 14 |
| Tightening torque | 0.8 Nm ... 1.2 Nm (PE connection) |
| 0.5 Nm ... 0.8 Nm (Mounting screws for mounting in the HEAVYCON housing) | |
| 0.5 Nm ... 0.8 Nm | |
| Stripping length of the individual wire | 8 mm |
Electrical properties
| Rated voltage (III/3) | 500 V |
| Rated surge voltage | 6 kV |
| Rated current | 16 A |
| SCCR | 5 kA (UL 2237) |
Mechanical properties
| Mechanical data | |
| Insertion/withdrawal cycles | ≥ 500 |
Material specifications
| Flammability rating according to UL 94 | V0 |
| Contact material | Copper alloy |
| Contact surface material | Ag |
| Contact carrier material | PC |
| Standards/regulations | PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) |
Environmental and real-life conditions
| Ambient conditions | |
| Ambient temperature (operation) | -40 °C ... 125 °C (including heating up of contacts) |
Standards and regulations
| Constructional and testing regulations | DIN EN 61984 |
| DIN EN 60664 | |
| IEC 60352 | |
| Tests | DIN EN 61984 |
| DIN EN 60664 | |
| IEC 60352 | |
| Testing | |
| Standards/regulations | PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) |