View larger
Images are for illustrative purposes only. Please refer to data sheet for details
HC-B 16-I-CT-F-32 1584923 PHOENIX CONTACT Contact insert
HC-B 16-I-CT-F-32
1584923
PHOENIX CONTACT
1 Pcs.
Contact insert
Contact insert, number of poles: 16+PE, size: B16, Female, Crimped connection, 500 V, 16 A, 0.5 mm² ... 4 mm²
Contact insert, number of positions: 16+PE, size: B16, Socket, Crimp connection, 500 V, 16 A, 0.5 mm2 ... 4 mm2
Connectors > Contact insert for rectangular connectors
Industrial plug-in connectors/interfaces
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact contact insert (part number HC-B 16-I-CT-F-32) operates as a multi-position female contact block designed to organize extensive control and signal wiring inside B16 industrial connector frames.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- General: Connectors may be operated only when there is no load/voltage.
- Assembly note: To ensure correct use, installation in housing with IP54 protection or better is required
- Product type: Contact insert with a fixed no. of positions
- Series: HC-B
- Type: B16
- Number of positions: 16
- Connection profile: 16+PE
- Contact numbering: 17 - 32
- Contact material type: turned
- Data management status Article revision: 11
- Insulation characteristics Overvoltage category: III
- Degree of pollution: 3
- Width: 34 mm
- Height: 34.6 mm
- Length: 84 mm
- Drill hole distance, horizontal: 77.5 mm
More info
▲Technical data
Notes
| General | For HEAVYCON ADVANCE housing of B16 type and HEAVYCON housing of B16/B32 type, crimp contacts CK 2,5-ED (crimp contacts not included in the scope of supply). |
| General | Connectors may be operated only when there is no load/voltage. |
Mounting
| Assembly note | To ensure correct use, installation in housing with IP54 protection or better is required |
| Remove the crimp contact using a screwdriver. The opening for the screwdriver is next to the opening where the conductor is inserted. |
Product properties
| Product type | Contact insert with a fixed no. of positions |
| Series | HC-B |
| Type | B16 |
| B32 | |
| Number of positions | 16 |
| Connection profile | 16+PE |
| Contact numbering | 17 - 32 |
| Contact material type | turned |
| Data management status | |
| Article revision | 11 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
Dimensions
| Dimensional drawing | |
| Width | 34 mm |
| Height | 34.6 mm |
| Length | 84 mm |
| Drill hole distance, horizontal | 77.5 mm |
| Mechanical characteristics | |
| Contact diameter | 2.5 mm |
Connection data
| Connection technology | |
| Connection technology | Crimp connection |
| Connection in acc. with standard | IEC / EN |
| Conductor connection | |
| Conductor cross section | 0.5 mm² ... 4 mm² |
| Connection cross section AWG | 20 ... 12 |
| Tightening torque | 0.8 Nm ... 1.2 Nm (PE connection) |
| 0.5 Nm ... 0.8 Nm (Mounting screws for mounting in the HEAVYCON housing) | |
| Stripping length of the individual wire | 7.5 mm |
Electrical properties
| Rated voltage (III/3) | 500 V |
| Rated surge voltage | 6 kV |
| Rated current | 16 A |
| SCCR | 5 kA (UL 2237) |
Mechanical properties
| Mechanical data | |
| Insertion/withdrawal cycles | ≥ 500 |
Material specifications
| Flammability rating according to UL 94 | V0 |
| Contact material | Copper alloy |
| Contact surface material | Ag (alternatively Au) |
| Contact carrier material | PC |
| Standards/regulations | PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) |
Environmental and real-life conditions
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 125 °C (including heating up of contacts) |
Standards and regulations
| Constructional and testing regulations | DIN EN 61984 |
| DIN EN 60664 | |
| IEC 60352 | |
| Tests | DIN EN 61984 |
| DIN EN 60664 | |
| IEC 60352 | |
| Testing | |
| Standards/regulations | PC: Fire protection in rail vehicles - requirement sets R22, R23, and R24 acc. to DIN EN 45545-2 (Risk level HL1 - HL3) |