View larger
PSR-SCP-42-230UC/URM4/4NO/2NC 2702924 PHOENIX CONTACT Extension module
PSR-SCP-42-230UC/URM4/4NO/2NC
2702924
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This Phoenix Contact PSR-SCP-42-230UC/URM4/4NO/2NC 2702924 PHOENIX CONTACT Extension module is an expansion device utilized in safety-critical industrial installations to extend the switching capacity and contact count of primary safety relays. Units of this type integrate into control cabinets to monitor and manage machine safety circuits efficiently. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Expansion device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): No
- Suitable for monitoring of proximity switches (EF007267): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): No
- Release-delay (EF001129): 0.1 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 22.5 mm
- Height (EF000040): 99 mm
- Depth (EF000049): 114.5 mm
More info
▲Key Commercial Data
| Orderkey | 2702924 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 263 (C-6-2017) |
| GTIN | 4055626429106 |
| Weight per Piece (excluding packing) | 199.000 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 55 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | 42 V AC/DC ... 230 V AC/DC -15 % ... +10 % (Rated control circuit supply voltage US) |
|---|---|
| Rated control supply current IS | typ. 35 mA (42 V DC) |
| typ. 15 mA (230 V AC) | |
| Power consumption at US | max. 1.5 W (with DC) |
| max. 1.7 W (with AC) | |
| Inrush current | < 38 A (Δt = 50 µs at Us) |
| Typ. starting time with Us | < 100 ms (when controlled via A1) |
| Typical release time | < 20 ms (Control via A1 at 42 V DC) |
| < 200 ms (Control via A1 at 230 V AC) | |
| Recovery time | < 1 s |
| Operating voltage display | 1 x green LED |
| Protective circuit | Surge protection Suppressor diode and varistors |
| Maximum switching frequency | 0.5 Hz |
Output data
| Contact type | 4 enabling current paths |
|---|---|
| 1 confirmation current path | |
| 1 signaling current path | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact, pay attention to the derating) |
| 1 A (N/C contact 51/52) | |
| 6 A (N/C contact 61/62) | |
| Maximum inrush current | 8 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2(observe derating) |
| Interrupting rating (ohmic load) max. | 1500 VA (N/O contact, 250 V AC, τ = 0 ms) |
| For additional values, see load curve | |
| Maximum interrupting rating (inductive load) | 48 W (N/O contact, 24 V DC, τ = 40 ms) |
| 40 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 36 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 35 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 33 W (N/O contact, 220 V DC, τ = 40 ms) | |
| 1500 VA (N/O contact, 250 V AC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Mechanical service life | 10x 106cycles |
| Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Output fuse | 6 A gL/gG (N/O contact and N/C contact 61/62) |
| 4 A gL/gG (N/O contact and N/C contact 61/62 for low-demand applications) | |
| 1 A gL/gG (N/C contact 51/52) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 199 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
Connection data
| Connection method | Screw connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 3 (In conjunction with suitable evaluating device) |
| Designation | EN ISO 13849 |
| Performance level (PL) | e (In conjunction with suitable evaluating device) |
| Category | 4 (In conjunction with suitable evaluating device) |
| Designation | EN 62061 |
| Safety Integrity Level Claim Limit (SIL CL) | 3 (In conjunction with suitable evaluating device) |
| Designation | EN 50156 |
| Safety Integrity Level (SIL) | 3 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178/VDE 0160 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV: between (A1/A2) and the remaining current paths between (51/52) and the remaining current paths between (61/62) and the remaining current paths between (13/14, 23/24, 33/34, 43/44) and the remaining current paths |
| 4 kV basic insulation between enabling current paths | |
| Basic insulation 4 kV between all current paths and housing | |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |