View larger
HC-M-01-AT-M-40-PE 1417382 PHOENIX CONTACT Contact insert module
HC-M-01-AT-M-40-PE
1417382
PHOENIX CONTACT
2 Pcs.
Connectors > Contact insert for rectangular connectors
Industrial plug-in connectors/interfaces
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for heavy-duty industrial connector frames, this Phoenix Contact HC-M-01-AT-M-40-PE contact insert module handles high-current power distribution requirements. Modular contact inserts allow engineers to build customized connector layouts that combine power and signal lines within a single housing. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of power contacts (EF012216): 0
- Number of control contacts (EF012217): 0
- Contact insert without contacts (EF007324): No
- Contact type (EF001587): Pin
- Number of poles (EF001391): 1
- Diameter plug-in contact (EF007320): 9.5 mm
- Ambient temperature (EF002386): 125 °C
- Operating temperature (EF002393): -40 °C
- Type of electric connection (EF003961): Axial screw connection
- With wire protection (EF000550): No
- Connectable conductor cross section multi-wired (EF007343): 25 mm²
- Material of contact surface (EF004020): Silver
- Material contact (EF007544): Copper
- With protective conductor (EF007468): Yes
- Min. number of insertion cycles (EF012212): 500
- Width (EF000008): 29.85 mm
More info
▲Key Commercial Data
| Orderkey | 1417382 |
|---|---|
| Packing unit | 2 pc |
| Minimum order quantity | 2 pc |
| Catalog page | Page 563 (C-2-2017) |
| GTIN | 4055626112633 |
| Weight per Piece (excluding packing) | 92.550 g |
| Custom tariff number | 85366990 |
| Country of origin | PL (Poland) |
Mechanical characteristics
| Conductor cross section | 25 mm² ... 70 mm² (The cross section specification refers to the geometric cross section of the cable used) |
|---|---|
| Connection cross section AWG | 10 ... 00 |
| Stripping length of the individual wire | 16 mm |
| Tightening torque | 8 Nm (25 mm² ... 70 mm²) |
| 9 Nm (50 mm²) | |
| 10 Nm (70 mm²) | |
| Contact diameter | 9.5 mm |
| Wire diameter including insulation | 12 mm (25 mm²) |
| 16 mm (40 mm²) | |
| Hexagonal socket | WAF 5 |
| Insertion/withdrawal cycles | ≥ 500 |
| Minimum housing height | 72 mm |
General
| Note | For HEAVYCON HC-B6 to B48 housing (housing height: min. 72 mm), HC-M-B..-MF-... module carrier frame required, axial connection for 5 mm Allen key |
|---|---|
| The axial screw connection must be established using a 5 mm Allen key (for stranded conductors only) | |
| Series | HC-M-HS |
| Color | light gray |
| Number of module slots | 2 |
| Connection method | Axial screw connection |
| Contact type | turned |
| Flammability rating according to UL 94 | V0 |
| Assembly instructions | To ensure correct use, installation in housing with IP54 protection or better is required |
| Connection | Note regarding axial connection technology: Only for stranded wires. The specified conductor cross sections refer to the geometric cross section of the cable used. Cables with a geometric cross section which deviates significantly from the nominal cable cross section must be checked before use. The axial connection technology connection space is designed for fine strand cables according to VDE 0295 Class 5. Deviating cable structures (e.g., Class 6 cables) must be checked before use. Assembly instructions Before assembly, ensure that the tapered screw is fully loosened (chamber is open). Cables must not be twisted. The wires must be pushed into the contact chamber as far as they will go (until the insulation touches the contact). Hold the wires in position and tighten using an Allen key. The used wire end must be cut off before reconnection. The terminal screw must only be retightened once to prevent the litz wires from breaking. To prevent damage to the contact, the wire/cable must be mechanically held at an appropriate distance from the connection point (e.g., when used in a plate cut out). For notes on correct execution, see DIN VDE 0100-520:2003-06. Unused connections must be tightened with maximum torque. |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |