View larger
MACX MCR-S-MUX 2865599 PHOENIX CONTACT HART multiplexer
MACX MCR-S-MUX
2865599
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - communication module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MACX MCR-S-MUX 2865599 PHOENIX CONTACT HART multiplexer is deployed in process automation applications to collect and distribute HART communication data from multiple field devices to control systems or asset management software. Multiplexers streamline diagnostic monitoring and configuration tasks for intelligent instrumentation networks.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- IO link master (EF007298): No
- System accessory (EF004118): Yes
- With potential separation (EF003272): No
- Suitable for rail mounting (EF003972): Yes
- Wall mounting/direct mounting (EF007020): No
- Front built-in possible (EF007016): No
- Rack-assembly possible (EF007018): No
- Suitable for safety functions (EF001597): No
- Appendant operation agent (Ex ia) (EF004141): No
- Appendant operation agent (Ex ib) (EF004142): No
- Width (EF000008): 35.2 mm
- Height (EF000040): 108.8 mm
- Depth (EF000049): 113.55 mm
More info
▲Key Commercial Data
| Orderkey | 2865599 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 166 (C-5-2017) |
| GTIN | 4046356153898 |
| Weight per Piece (excluding packing) | 211.400 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
Field devices interface (HART)
| Channels | 16 or 32; adjustable using a switch |
|---|---|
| Connection method | Flat-ribbon cable, 14-pos. (inclusive) |
| Signal | HART FSK |
| HART specification | HART Field Communication Protocol Rev. 6.0 (downward compatible up to Rev 4.0); FSK Physical Layer Specification (Rev. 8.1) |
| Data transmission display | Two yellow "Tx" and "Rx" "HART" LEDs |
| Display error | Red "ERR" LED (flashes in case of an error in the HART bus) |
RS-485 interface
| Connection method | D-SUB-9 female connector |
|---|---|
| Signal | RS-485 |
| Data flow control/protocols | Compatible with OPC HART server, PDM, PRM, and FDT/DTM |
| Number of HART multiplexers per bus segment | Max 31 |
| Address setting | 0...127; using a rotary switch at the front |
| Data rate | 9600 / 19200 / 38400 / 57600 [bps]; via rotary switch at the front |
| Transmission length | ≤ 1200 m |
| Display | Two yellow "Tx" and "Rx" "RS-485" LEDs |
General data
| Supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 18 V ... 31.2 V |
| Typical current consumption | 55 mA |
| Nominal power consumption | 1.35 W |
| Operating voltage display | Green "PWR" LED |
| Undervoltage monitoring | Yes (no faulty devices / output states) |
| Galvanic isolation of HART signal/RS-485 | 350 V AC |
| Galvanic isolation of HART signals between each other | 100 V DC (capacitive) |
| Galvanic isolation of HART signal/supply | 350 V AC |
| Galvanic isolation of RS-485/supply | 350 V AC |
| Error monitoring | Processor error: The "PWR" LED flashes; error in the HART communication: the "ERR" LED flashes |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |