View larger
GW PL HART8+AI-BUS 2702236 PHOENIX CONTACT Protocol converter
GW PL HART8+AI-BUS
2702236
PHOENIX CONTACT
1 Pcs.
Automation > PLC communication module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact Protocol converter unit, bearing part number GW PL HART8+AI-BUS, provides specialized signal conditioning and protocol translation for process instrumentation networks. Devices of this kind integrate smart field instruments into control systems, converting field measurements into standardized parameters for continuous monitoring. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for TCP/IP (EF003050): No
- Supporting protocol for PROFIBUS (EF003052): No
- Supporting protocol for CAN (EF003053): No
- Supporting protocol for INTERBUS (EF003054): No
More info
▲Key Commercial Data
| Orderkey | 2702236 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 521 (C-6-2017) |
| GTIN | 4055626067070 |
| Weight per Piece (excluding packing) | 342.400 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| -40 °F ... 158 °F | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
General
| Test voltage data interface/power supply | 500 V AC |
|---|---|
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Net weight | 342.4 g |
| Color | gray |
| MTBF | 208 Years (Siemens model SN29500, temperature 40°C, env. factor 1.5 and stress factor 50%) |
| Conformance | CE-compliant |
Power supply
| Supply voltage range | 19.2 V DC ... 30 V DC (supplied from the bus) |
|---|---|
| Max. current consumption | 258 mA (at 24 V DC) |
| Typical current consumption | 74 mA (24 V DC with no load) |
Serial interface
| Interface 1 | HART FSK |
|---|---|
| Interface | Analog |
| No. of ports | 8 |
| Connection method | Screw connection |
| Maximum output current | 25 mA (per channel) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
|---|---|
| Conformance | CE-compliant |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| ATEX | II 3 G Ex nA IIC T4 Gc DEMKO 17 ATEX 1749X |
| IECEx | IECEx ULD 17.0020X Ex nA IIC T4 Gc |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |