View larger
GW PL ETH/UNI-BUS 2702233 PHOENIX CONTACT Ethernet HART multiplexer
GW PL ETH/UNI-BUS
2702233
PHOENIX CONTACT
1 Pcs.
Automation > PLC communication module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The GW PL ETH/UNI-BUS 2702233 PHOENIX CONTACT Ethernet HART multiplexer functions as a gateway component to aggregate field device data for supervisory control systems. Multiplexers of this type are widely implemented in process automation environments to streamline maintenance and data collection routines.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Radio standard Bluetooth (EF007178): No
- Radio standard WLAN 802.11 (EF007179): No
- Radio standard GPRS (EF008523): No
- Radio standard GSM (EF008524): No
- Radio standard UMTS (EF008525): No
More info
▲Key Commercial Data
| Orderkey | 2702233 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 521 (C-6-2017) |
| GTIN | 4055626067049 |
| Weight per Piece (excluding packing) | 216.900 g |
| Custom tariff number | 85176200 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| -40 °F ... 158 °F | |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
General
| Test voltage data interface/power supply | 500 V AC |
|---|---|
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Net weight | 216.9 g |
| Color | gray |
| MTBF | 292 Years (Siemens model SN29500, temperature 40°C, env. factor 1.5 and stress factor 50%) |
| Conformance | CE-compliant |
Power supply
| Supply voltage range | 19.2 V DC ... 30 V DC |
|---|---|
| Max. current consumption | 63 mA (at 24 V DC) |
| Typical current consumption | 46 mA (at 24 V DC) |
Serial interface
| Interface 1 | Bus |
|---|---|
| Transmission length | ≤ 100 m |
| Output nominal voltage | 24 V DC |
| Maximum output current | 3.937 A (per station) |
| Interface 2 | Modbus/TCP, HART IP, PROFINET |
| Interface | Ethernet 10/100Base T |
| Connection method | RJ45 socket, auto negotiation and auto crossing |
| Protocols supported | Modbus/TCP, HART IP, PROFINET |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
|---|---|
| Conformance | CE-compliant |
| Noxious gas test | ISA-S71.04-1985 G3 Harsh Group A |
| ATEX | II 3 G Ex nA IIC T4 Gc DEMKO 17 ATEX 1749X |
| IECEx | IECEx ULD 17.0020X Ex nA IIC T4 Gc |
| UL, USA/Canada | Class I, Div. 2, Groups A, B, C, D |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |