Request QuoteProduct Overview
The UKH 70-PE/S ground modular terminal block by Phoenix Contact handles heavy-duty grounding requirements in large-scale industrial distribution systems and machinery. High-capacity ground terminals anchor thick conductive cables to standard mounting rails to protect equipment from electrical faults. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- PEN function possible (EF002544): No
- Connectable conductor cross section solid-core (EF007337): 16 mm²
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of clamp positions per level (EF002660): 2
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Operating temperature (EF002393): -60 °C
- Width (EF000008): 20.3 mm
- Height (EF000040): 70.5 mm
- Closing plate required (EF002525): No
- Colour (EF000007): Green/yellow
More info
▲Key Commercial Data
| Orderkey | 3213141 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 259 (C-1-2017) |
| GTIN | 4046356783446 |
| Weight per Piece (excluding packing) | 198.000 g |
| Custom tariff number | 85369010 |
| Country of origin | CN (China) |
General
| Number of positions | 1 |
|---|---|
| Number of levels | 1 |
| Number of connections | 2 |
| Nominal cross section | 70 mm² |
| Color | green-yellow |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Open side panel | No |
| Terminal block mounting | 6 Nm ... 8 Nm (PE foot with mounting screw, M6) |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1= 5 Hz to f2= 150 Hz |
| ASD level | 1.857 (m/s2)2/Hz |
| Acceleration | 0,8 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5 g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Note | Please observe the current carrying capacity of the DIN rails. |
|---|---|
| Connection method | Screw connection |
| Screw thread | M8 |
| Stripping length | 24 mm |
| Tightening torque, min | 8 Nm |
| Tightening torque max | 10 Nm |
| Connection in acc. with standard | IEC 60947-7-2 |
| Conductor cross section solid min. | 16 mm² |
| Conductor cross section solid max. | 95 mm² |
| Conductor cross section AWG min. | 4 |
| Conductor cross section AWG max. | 3/0 |
| Conductor cross section flexible min. | 25 mm² |
| Conductor cross section flexible max. | 70 mm² |
| Min. AWG conductor cross section, flexible | 3 |
| Max. AWG conductor cross section, flexible | 2/0 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 16 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 70 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 16 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 70 mm² |
| Internal cylindrical gage | A11 |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-2 |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |