View larger
UT 4-PE/L/L 3214360 PHOENIX CONTACT Ground modular terminal block
UT 4-PE/L/L
3214360
PHOENIX CONTACT
50 Pcs.
Automation > Ground terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact ground modular terminal block, part number UT 4-PE/L/L 3214360, provides secure conductor termination and protective earth grounding inside industrial control panels. Terminal blocks like this are routinely integrated onto standard rails to distribute control signals and safely organize earth continuity across complex wiring architectures.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- PEN function possible (EF002544): No
- Connectable conductor cross section solid-core (EF007337): 0.14 mm²
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of clamp positions per level (EF002660): 2
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Width (EF000008): 6.2 mm
- Height (EF000040): 92.7 mm
- Depth (EF000049): 60.1 mm
- Closing plate required (EF002525): No
- Colour (EF000007): EV000270
More info
▲Key Commercial Data
| Orderkey | 3214360 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Catalog page | Page 230 (C-1-2017) |
| GTIN | 4046356895682 |
| Weight per Piece (excluding packing) | 31.340 g |
| Custom tariff number | 85369010 |
| Country of origin | PL (Poland) |
General
| Number of levels | 3 |
|---|---|
| Number of connections | 5 |
| Potentials | 3 |
| Nominal cross section | 4 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.02 W (the value is multiplied when connecting multiple levels) |
| Maximum load current | 36 A (with 6 mm² conductor cross section) |
| Nominal current IN | 30 A |
| Nominal voltage UN | 500 V |
| Maximum load current | 36 A (with 6 mm² conductor connection) |
| Nominal current IN | 30 A (with 4 mm² conductor cross section) |
| Nominal voltage UN | 500 V |
| Open side panel | No |
| Shock protection test specification | IEC 60529:2001-02 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 7.3 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.14 mm² / 0.2 kg |
| 4 mm² / 0.9 kg | |
| 6 mm2/ 1.4 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.14 mm² |
| Tractive force setpoint | 10 N |
| Conductor cross section tensile test | 4 mm² |
| Tractive force setpoint | 60 N |
| Conductor cross section tensile test | 6 mm² |
| Tractive force setpoint | 80 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 0.48 kA |
| Conductor cross section short circuit testing | 6 mm² |
| Short-time current | 0.72 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1= 5 Hz to f2= 150 Hz |
| ASD level | 0.964 (m/s2)2/Hz |
| Acceleration | 0.58 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5 g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
Connection data
| Note | Please observe the current carrying capacity of the DIN rails. |
|---|---|
| Connection method | Screw connection |
| Screw thread | M3 |
| Stripping length | 9 mm |
| Tightening torque, min | 0.6 Nm |
| Tightening torque max | 0.8 Nm |
| Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 |
| Conductor cross section solid min. | 0.14 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible min. | 0.14 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 26 |
| Max. AWG conductor cross section, flexible | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| Internal cylindrical gage | A4 |
| Connection method | Screw connection |
| Screw thread | M3 |
| Stripping length | 9 mm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Tightening torque, min | 0.6 Nm |
| Tightening torque max | 0.8 Nm |
| Conductor cross section solid min. | 0.14 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible min. | 0.14 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 26 |
| Max. AWG conductor cross section, flexible | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-1/IEC 60947-7-2 |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |