View larger
PT 16-TWIN N-PE 3208786 PHOENIX CONTACT Ground modular terminal block
PT 16-TWIN N-PE
3208786
PHOENIX CONTACT
25 Pcs.
Automation > Ground terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact part number PT 16-TWIN N-PE (PT 16-TWIN N-PE 3208786 PHOENIX CONTACT Ground modular terminal block) is a ground modular terminal block designed to establish secure protective earth connections in industrial control panels and distribution boards. Terminal blocks of this type route ground fault currents safely to the mounting rail, protecting equipment and operators from electrical hazards. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Ground terminal block
- Area of application: Railway industry
- Number of connections: 3
- Number of rows: 1
- Data management status Article revision: 10
- Insulation characteristics Overvoltage category: III
- Degree of pollution: 3
- Rated surge voltage: 8 kV
- Maximum power dissipation for nominal condition: 2.43 W
- Grounding foot: Yes
- Number of connections per level: 3
- Nominal cross section: 16 mm²
- Note: Please observe the current carrying capacity of the DIN rails.
- Stripping length: 18 mm ... 20 mm
- Internal cylindrical gage: A7
- Connection in acc. with standard: IEC 60947-7-2
More info
▲| Product type | Ground terminal block |
| Area of application | Railway industry |
| Machine building | |
| Plant engineering | |
| Number of connections | 3 |
| Number of rows | 1 |
| Data management status | |
| Article revision | 10 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Rated surge voltage | 8 kV |
| Maximum power dissipation for nominal condition | 2.43 W |
| Grounding foot | Yes |
| Number of connections per level | 3 |
| Nominal cross section | 16 mm² |
| Note | Please observe the current carrying capacity of the DIN rails. |
| Stripping length | 18 mm ... 20 mm |
| Internal cylindrical gage | A7 |
| Connection in acc. with standard | IEC 60947-7-2 |
| Conductor cross section rigid | 0.5 mm² ... 25 mm² |
| Cross section AWG | 20 ... 4 (converted acc. to IEC) |
| Conductor cross section flexible | 0.5 mm² ... 25 mm² |
| Conductor cross section, flexible [AWG] | 20 ... 4 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 16 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 16 mm² |
| Nominal cross section | 16 mm² |
| Connection cross sections directly pluggable | |
| Conductor cross section rigid | 2.5 mm² ... 25 mm² |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 2.5 mm² ... 16 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 2.5 mm² ... 16 mm² |
| Rated data (ATEX/IECEx) | |
| Identification | II 2 GD Ex eb IIC Gb |
| Operating temperature range (1) | -60 °C ... 85 °C |
| Operating temperature range (2) | -40 °C ... 110 °C |
| Ex-certified accessories | 3208799 D-PT 16-TWIN N |
| 1204517 SZF 1-0,6X3,5 | |
| 3022276 CLIPFIX 35-5 | |
| 3022218 CLIPFIX 35 | |
| output | (Permanent) |
| Ex connection data General | |
| Nominal cross section | 16 mm² |
| Rated cross section AWG | 6 |
| Connection capacity rigid | 0.5 mm² ... 25 mm² |
| Connection capacity AWG | 20 ... 4 |
| Connection capacity flexible | 0.5 mm² ... 16 mm² |
| Connection capacity AWG | 20 ... 6 |
| Width | 12.2 mm |
| End cover width | 2.2 mm |
| Height | 100.2 mm |
| Depth | 53.3 mm |
| Depth on NS 35/7,5 | 52.6 mm |
| Depth on NS 35/15 | 60.1 mm |
| Color | green-yellow |
| Flammability rating according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static insulating material application in cold | -60 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Mechanical data | |
| Open side panel | Yes |
| Oscillation/broadband noise | |
| Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Spectrum | Service life test category 2, bogie-mounted |
| Frequency | f1= 5 Hz to f2= 250 Hz |
| ASD level | 6.12 (m/s²)²/Hz |
| Acceleration | 3.12g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Result | Test passed |
| Shocks | |
| Specification | DIN EN 50155 (VDE 0115-200):2008-03 |
| Pulse shape | Half-sine |
| Acceleration | 30g |
| Shock duration | 18 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Result | Test passed |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (operation) | 20 % ... 90 % |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Connection in acc. with standard | IEC 60947-7-2 |
| Mounting type | NS 35/7,5 |
| NS 35/15 |