Phoenix Contact TTC-6P-2X1-24DC-UT-I surge protection, consisting of protective plug and base element, is installed in control cabinets to safeguard sensitive electronics and signal circuits from transient overvoltages and voltage spikes. Units of this type help prevent costly downtime and equipment failure in industrial automation environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2906810
- Packing unit: 1 pc
- Catalog page: Page 128 (C-4-2019)
- GTIN: 4055626135748
- Weight per Piece (excluding packing): 40.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 105.8 mm
- Width: 6.2 mm +0.1 mm
- Depth: 100 mm (incl. DIN rail 7.5 mm)
- Ambient temperature (operation): -40 °C ... 85 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Permissible humidity (operation): 5 % ... 95 %
- Altitude: ≤ 4000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PBT
More info
▲Key Commercial Data
| Orderkey | 2906810 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 128 (C-4-2019) |
| GTIN | 4055626135748 |
| Weight per Piece (excluding packing) | 40.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 85 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 5 % ... 95 % |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | traffic grey A RAL 7042 |
| light grey RAL 7035 | |
| Mounting type | DIN rail: TH 35 - 7.5 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 600 mA (56 °C) |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 10 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 0.5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Voltage protection level Up(line-earth) | ≤ 140 V (C1 - 1 kV/500 A) |
| ≤ 190 V (C2 - 10 kV / 5 kA) | |
| ≤ 45 V (C3 - 25 A) | |
| ≤ 50 V (C3 - 100 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 55 V (C1 - 1 kV/500 A) |
| ≤ 120 V (C2 - 10 kV / 5 kA) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 270 kHz/150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 960 kHz |
| Capacity (line-earth) | typ. 2.2 nF |
| Resistance per path | 1.65 Ω ±20 % |
| Max. required back-up fuse | 630 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 500 A | |
| Pulse reset time (line-earth) | ≤ 300 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27140201 |
|---|---|
| eCl@ss 4.1 | 27130801 |
| eCl@ss 5.0 | 27130801 |
| eCl@ss 5.1 | 27130801 |
| eCl@ss 6.0 | 27130800 |
| eCl@ss 7.0 | 27130807 |
| eCl@ss 8.0 | 27130807 |
| eCl@ss 9.0 | 27130807 |
UNSPSC
| UNSPSC 6.01 | 30212010 |
|---|---|
| UNSPSC 7.0901 | 39121610 |
| UNSPSC 11 | 39121610 |
| UNSPSC 12.01 | 39121610 |
| UNSPSC 13.2 | 39121620 |
| UNSPSC 18.0 | 39121620 |
| UNSPSC 19.0 | 39121620 |
| UNSPSC 20.0 | 39121620 |
| UNSPSC 21.0 | 39121620 |