View larger
IB IL PWM/2-PAC 2861632 PHOENIX CONTACT Inline function terminal
IB IL PWM/2-PAC
2861632
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - function-/technology module
I/O
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for modular automation architectures, the IB IL PWM/2-PAC 2861632 PHOENIX CONTACT Inline function terminal provides pulse-width modulation output capabilities for controlling proportional valves, heaters, and DC motors. These terminal modules allow automation systems to deliver variable power outputs efficiently within industrial control assemblies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of functions (EF003244): 1
- Number of HW-interfaces industrial Ethernet (EF003020): 0
- Number of interfaces PROFINET (EF006932): 0
- Number of HW-interfaces RS-232 (EF003021): 0
- Number of HW-interfaces RS-422 (EF003022): 0
- Number of HW-interfaces RS-485 (EF003023): 0
- Number of HW-interfaces serial TTY (EF003024): 0
- Number of HW-interfaces parallel (EF003026): 0
- Number of HW-interfaces wireless (EF006933): 0
- Number of HW-interfaces USB (EF003025): 0
- Number of HW-interfaces other (EF003027): 0
- With optical interface (EF003028): No
- Supporting protocol for EtherCAT (EF017564): No
- Supporting protocol for TCP/IP (EF003050): No
- Supporting protocol for PROFIBUS (EF003052): Yes
- Supporting protocol for CAN (EF003053): No
More info
▲Key Commercial Data
| Orderkey | 2861632 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 180 (C-6-2017) |
| GTIN | 4017918948313 |
| Weight per Piece (excluding packing) | 165.100 g |
| Custom tariff number | 85389091 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 95 % (non-condensing) |
| Air pressure (operation) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 70 kPa ... 106 kPa (up to 3000 m above sea level) |
| Degree of protection | IP20 |
General
| Mounting type | DIN rail |
|---|---|
| Net weight | 163 g |
| Note on weight specifications | with connectors |
| Operating mode | Process data operation with 2 words |
| Diagnostics messages | Short circuit or overload of a 24 V output Yes |
Interfaces
| Designation | Inline local bus |
|---|---|
| No. of channels | 2 |
| Connection method | Inline data jumper |
| Transmission speed | 500 kbps |
Inline potentials
| Designation | Communications power (UL) |
|---|---|
| Supply voltage | 7.5 V DC (via voltage jumper) |
| Current consumption | max. 130 mA |
| Power consumption | max. 0.98 W |
| Designation | Segment circuit supply (US) |
| Supply voltage | 24 V DC (via voltage jumper) |
| Current consumption | max. 1 A |
| 0 A |
Digital outputs
| Output name | Digital output: 24 V DC |
|---|---|
| Connection technology | 2-wire (shielded) |
| Number of outputs | 2 |
| Type of protection | Short-circuit protection, overload protection of the outputs |
| Output voltage | 24 V |
| Nominal output voltage | 24 V DC |
| Maximum output current per module / terminal block | 1 A |
| Nominal load, inductive | 12 VA (1.2 H, 24 Ω) |
| Nominal load, lamp | 12 W |
| Nominal load, ohmic | 12 W |
| Output name | Digital output: 5 V DC |
| Connection technology | 2-wire (shielded) |
| Maximum operating frequency with ohmic nominal load | 50 kHz |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |