PHOENIX CONTACT PTFIX 6X1,5-NS15A BK PTFIX 6X1,5-NS15A BK 3002967 PHOENIX CONTACT Distribution block View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PTFIX 6X1,5-NS15A BK 3002967 PHOENIX CONTACT Distribution block

PTFIX 6X1,5-NS15A BK

3002967

PHOENIX CONTACT

20 Pcs.

Distribution block Distribution block, internally bridged, rated voltage: 500 V, rated current: 17.5 A, number of connections: 6, connection type: Push-in connection, cross-section: 0.14 mm² - 2.5 mm², mounting class: NS 15, color: black

Automation > Feed-through terminal block
FIX block System

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact PTFIX 6X1,5-NS15A BK distribution block allows engineers to quickly split power and control potentials within compact industrial switchgear. This factory-configured block minimizes wiring effort and saves valuable rail space.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated current In (EF008250): 17.5 A
  • Rated voltage (EF000228): 500 V
  • Number of clamp positions per level (EF002660): 6
  • Mounting method (EF000003): DIN rail (top hat rail) 15 mm
  • Width (EF000008): 12.5 mm
  • Height (EF000040): 21.6 mm
  • Depth (EF000049): 27.4 mm
  • Closing plate required (EF002525): No
  • Colour (EF000007): Black
  • Internally connected stages (EF002661): Yes

More info

▲

Key Commercial Data

Orderkey3002967
Packing unit20 pc
Minimum order quantity20 pc
NoteMade to Order (non-returnable)
Catalog pagePage 137 (C-1-2017)
GTIN4055626433752
Weight per Piece (excluding packing)5.870 g
Custom tariff number85369010
Country of originPL (Poland)

General

NoteNotes on operation The blocks can be bridged with one another via the conductor shaft. For corresponding plug-in bridges, see accessories
Notes on operation The D-PTFIX 1,5 cover (accessory) must be placed on the end of the terminal strip
Number of levels1
Number of connections6
Potentials1
Nominal cross section1.5 mm²
Colorblack
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.56 W
Ambient temperature (operation)-60 °C ... 130 °C
Maximum load current22 A
Maximum total current26 A
Nominal current IN17.5 A
Nominal voltage UN500 V
Open side panelNo
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.14 mm² / 0.2 kg
1.5 mm² / 0.4 kg
Tensile test resultTest passed
Conductor cross section tensile test0.14 mm²
Tractive force setpoint10 N
Conductor cross section tensile test1.5 mm²
Tractive force setpoint40 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 15
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 3.2 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing1.5 mm²
Short-time current0.18 kA
Result of thermal testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Proof of thermal characteristics (needle flame) effective duration30 s
Result of aging testTest passed
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width12.5 mm
Length21.6 mm
Height NS 1527.4 mm

Connection data

Connection methodPush-in connection
Stripping length8 mm ... 10 mm
Connection in acc. with standardIEC 60947-7-1
Conductor cross section solid min.0.14 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section AWG min.26
Conductor cross section AWG max.14
Conductor cross section flexible min.0.14 mm²
Conductor cross section flexible max.1.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.1.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.1.5 mm²
Internal cylindrical gageA1 / B1

Standards and Regulations

Connection in acc. with standardIEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.