View larger
FLT-SEC-P-T1-264/50-P 2907391 PHOENIX CONTACT Type 1 surge protection plug
FLT-SEC-P-T1-264/50-P
2907391
PHOENIX CONTACT
10 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact type 1 surge protection plug provides heavy-duty suppression capabilities against severe direct lightning currents in electrical supplies. This pluggable module integrates seamlessly into primary distribution panels to maintain continuous surge suppression.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 2907391 |
|---|---|
| Packing unit | 5 pc |
| Minimum order quantity | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 34 (C-4-2017) |
| GTIN | 4055626197210 |
| Weight per Piece (excluding packing) | 259.900 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
General
| IEC test classification | I / II |
|---|---|
| T1 / T2 | |
| EN type | T1 / T2 |
| IEC power supply system | TT |
| Mode of protection | L-N |
| L-PEN | |
| Mounting type | on base element |
| Color | light grey RAL 7035 |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240 V AC (TN) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| Nominal discharge current In(8/20) µs | 50 kA |
| Maximum discharge current Imax(8/20) µs | 100 kA |
| Impulse discharge current (10/350) µs, charge | 25 As |
| Impulse discharge current (10/350) µs, specific energy | 625 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 50 kA |
| Follow current interrupt rating Ifi | 50 kA |
| Short-circuit current rating ISCCR | 50 kA |
| Voltage protection level Up | ≤ 2.5 kV |
| Residual voltage Ures | ≤ 2.5 kV (at In) |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 2.5 kV |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| 760 V AC (120 min / withstand mode) | |
| Response time tA | ≤ 100 ns |
| Max. backup fuse with branch wiring | 500 A (gG) |
UL specifications
| SPD Type | 1CA |
|---|---|
| Maximum continuous operating voltage MCOV | 264 V AC |
| Nom. voltage | 240 V AC |
| Mode of protection | L-N |
| L-G | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Voltage protection rating VPR | 1500 V |
| Nominal discharge current In | 20 kA |
| Short-circuit current rating (SCCR) | 50 kA |