View larger
FLKM-2KS40/PMT/YCS 2321907 PHOENIX CONTACT Passive module
FLKM-2KS40/PMT/YCS
2321907
PHOENIX CONTACT
1 Pcs.
Automation > Interface module
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact FLKM-2KS40/PMT/YCS passive module serves as an intermediary connection interface, facilitating error-free signal transmission between complex automation controllers and field-level instruments. Such passive units streamline panel integration by organizing multi-conductor cabling into clearly mapped connection points. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, field-sided (EF005525): Screw connection
- Number of poles (EF001391): 24
- Rated voltage (EF000228): 50 V
- Rated current (EF000227): 1 A
- Depth (EF000049): 57.1 mm
- Width (EF000008): 134.8 mm
- Height (EF000040): 77 mm
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
General
| Max. perm. operating voltage | < 60 V DC |
|---|---|
| < 50 V AC | |
| Max. perm. current (per branch) | 1 A |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Degree of protection | IP20 |
Connection data for connection 1
| Connection name | Field level |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data for connection 2
| Connection name | Controller level |
|---|---|
| Connection method | Yokogawa KS-compatible |
| Torque | 0.5 Nm |
| Number of connections | 2 |
| Number of positions | 40 |
Supported controller
| Controller | YOKOGAWA CS3000 CentumVP |
|---|---|
| - suitable I/O card | AAI135 |
| AAI835 | |
| Controller | YOKOGAWA STARDOM |
| - suitable I/O card | NFAI135 |
| NFAI835 |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | EN 50178 |
| Rated insulation voltage | 63 V |
| Rated surge voltage | 0.6 kV (basic insulation) |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |