View larger
PT 2,5-4L/1P-FS 3012302 PHOENIX CONTACT Flange
PT 2,5-4L/1P-FS
3012302
PHOENIX CONTACT
10 Pcs.
Automation > End bracket for terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT 2,5-4L/1P-FS is a flange component used to provide mechanical stability and secure fastening for multi-level modular terminal block assemblies. Flanges ensure proper alignment and mechanical reinforcement where terminal blocks interface with plug-in connectors or panel walls. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Flange
- Data management status Article revision: 02
- Width: 5.2 mm
- End cover width: 2.2 mm
- Height: 105.6 mm
- Depth on NS 35/7,5: 59 mm
- Depth on NS 35/15: 66.5 mm
- Color: gray (RAL 7042)
- Material: PA
- Flammability rating according to UL 94: V0
- Static insulating material application in cold: -60 °C
- Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3
- Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3
- Surface flammability NFPA 130 (ASTM E 162): passed
More info
▲| Product type | Flange |
| Data management status | |
| Article revision | 02 |
| Width | 5.2 mm |
| End cover width | 2.2 mm |
| Height | 105.6 mm |
| Depth on NS 35/7,5 | 59 mm |
| Depth on NS 35/15 | 66.5 mm |
| Color | gray (RAL 7042) |
| Material | PA |
| Flammability rating according to UL 94 | V0 |
| Static insulating material application in cold | -60 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Surge voltage test | |
| Result | Test passed |
| Temperature-rise test | |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Result | Test passed |
| Short-time withstand current 2.5 mm² | 0.3 kA |
| Result | Test passed |
| Power-frequency withstand voltage | |
| Test voltage setpoint | 1.89 kV |
| Result | Test passed |
| Mechanical strength | |
| Result | Test passed |
| Attachment on the carrier | |
| Result | Test passed |
| Test for conductor damage and slackening | |
| Rotation speed | 10 rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.14 mm² / 0.2 kg |
| 2.5 mm² / 0.7 kg | |
| 4 mm² / 0.9 kg | |
| Result | Test passed |
| Aging | |
| Temperature cycles | 192 |
| Result | Test passed |
| Needle-flame test | |
| Time of exposure | 30 s |
| Result | Test passed |
| Oscillation/broadband noise | |
| Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
| Spectrum | Service life test category 1, class B, body mounted |
| Frequency | f1= 5 Hz to f2= 150 Hz |
| ASD level | 0.964 (m/s²)²/Hz |
| Acceleration | 0.58g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Result | Test passed |
| Shocks | |
| Specification | DIN EN 50155 (VDE 0115-200):2022-06 |
| Pulse shape | Half-sine |
| Acceleration | 5g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Result | Test passed |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C ... 105 °C (max. short-term operating temperature RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (storage/transport) | 30 % ... 70 % |