View larger
SOL-SC-2ST-0-DC-2MPPT-1000SE 1016812 PHOENIX CONTACT String combiner box (SCB)
SOL-SC-2ST-0-DC-2MPPT-1000SE
1016812
PHOENIX CONTACT
1 Pcs.
Automation > Photovoltaic DC Stringbox
Industry Solutions (IS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact SOL-SC-2ST-0-DC-2MPPT-1000SE string combiner box (SCB) collects DC power from multiple solar strings and delivers it securely to the primary inverter system. Such junction components are standard in commercial photovoltaic deployments to reduce cabling complexity and enhance system-wide safety. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1016812
- Packing unit: 1 pc
- GTIN: 4055626499154
- Weight per Piece (excluding packing): 2,250.000 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- System voltage: 1000 V DC (U max )
- Number of string inputs: 2 (per MPP tracker)
- Current per string (max.): 20 A (I max )
- Number of outputs: 1 (per MPP tracker)
- Number of supported MPP trackers: 2
- Surge protective device: T1 / T2
- Protection level U p: ≤ 3.5 kV
- Total discharge current I total (8/20) µs: 40 kA
- Total discharge current I total (10/350) µs: 5 kA
- Type of cable entry: Cable gland
More info
▲Key Commercial Data
| Orderkey | 1016812 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626499154 |
| Weight per Piece (excluding packing) | 2,250.000 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
System parameter
| System voltage | 1000 V DC (Umax) |
|---|---|
| Number of string inputs | 2 (per MPP tracker) |
| Current per string (max.) | 20 A (Imax) |
| Number of outputs | 1 (per MPP tracker) |
| Number of supported MPP trackers | 2 |
Safety equipment
| Surge protective device | T1 / T2 |
|---|---|
| Protection level Up | ≤ 3.5 kV |
| Total discharge current Itotal(8/20) µs | 40 kA |
| Total discharge current Itotal(10/350) µs | 5 kA |
Cable entry
| Type of cable entry | Cable gland |
|---|---|
| Cable cross section string input | 2.5 mm² ... 6 mm² |
| Sealing area string input | 3 mm ... 6.5 mm |
| Cable cross section output | 2.5 mm² ... 6 mm² |
| Sealing area output | 3 mm ... 6.5 mm |
| Cable cross section grounding | 16 mm² (2 x) |
| Sealing area grounding | 6 mm ... 12 mm |
General data
| Material cover/door | Polycarbonate (transparent) |
|---|---|
| Degree of protection | IP65 |
| Protection class | II |