View larger
FIP-3/3 SERVICE 3069312 PHOENIX CONTACT Interruption plug
FIP-3/3 SERVICE
3069312
PHOENIX CONTACT
1 Pcs.
Automation > Installation clamp for meters
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Facilitating temporary circuit redirection during testing sequences, the Phoenix Contact FIP-3/3 SERVICE interruption plug safely bridges multi-pole terminal arrays. Interruption plugs are heavily utilized in electrical testing facilities and substations for routine diagnostic measurements.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Plug
- Number of positions: 3
- Pitch: 8.2 mm
- Data management status Article revision: 05
- Insulation characteristics Overvoltage category: III
- Rated surge voltage: 4 kV
- Test surge voltage: 5 kV
- Nominal current: 20 A
- Maximum load current: 20 A
- Nominal voltage: 400 V
- Width: 24.5 mm
- Height: 53.4 mm
- Pitch: 8.2 mm
- Color: red (RAL 3001)
- Flammability rating according to UL 94: V0
- Insulating material group: I
More info
▲| Product type | Plug |
| Number of positions | 3 |
| Pitch | 8.2 mm |
| Data management status | |
| Article revision | 05 |
| Insulation characteristics | |
| Overvoltage category | III |
| Rated surge voltage | 4 kV |
| Test surge voltage | 5 kV |
| Nominal current | 20 A |
| Maximum load current | 20 A |
| Nominal voltage | 400 V |
| Width | 24.5 mm |
| Height | 53.4 mm |
| Pitch | 8.2 mm |
| Color | red (RAL 3001) |
| Flammability rating according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Mechanical data | |
| Open side panel | Yes |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C ... 85 °C |
| Ambient temperature (storage/transport) | -25 °C ... 55 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Mounting type | Insertion in base strip |