View larger
D-LAN-CAT.5-FP 2800723 PHOENIX CONTACT Surge protection device
D-LAN-CAT.5-FP
2800723
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Protection of Ethernet networks and data communication equipment from transient overvoltages is achieved using the Phoenix Contact D-LAN-CAT.5-FP surge protection device. This hardware category is installed inline on high-speed data lines to safeguard delicate network interface cards and controllers from electrical surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2800723
- Packing unit: 1 pc
- Catalog page: Page 143 (C-4-2017)
- GTIN: 4046356730273
- Weight per Piece (excluding packing): 90.000 g
- Custom tariff number: 85363010
- Country of origin: CN (China)
- Height: 110 mm
- Width: 28 mm
- Depth: 60 mm (incl. NS 35 adapter)
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: ABS
- Flammability rating according to UL 94: V0
- Color: gray
- Standards for cearances and creepage distances: IEC 60664
More info
▲Key Commercial Data
| Orderkey | 2800723 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 143 (C-4-2017) |
| GTIN | 4046356730273 |
| Weight per Piece (excluding packing) | 90.000 g |
| Custom tariff number | 85363010 |
| Country of origin | CN (China) |
General
| Housing material | ABS |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Color | gray |
| Standards for cearances and creepage distances | IEC 60664 |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Type | Attachment plug for DIN rail mounting |
| Number of positions | 8 |
| Direction of action | Line-Line & Line-Ground/Shield |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| VDE requirement class | B2 |
| C1 | |
| Maximum continuous voltage UC | ± 5 V DC |
| Maximum continuous voltage UC(wire-wire) | ± 5 V DC (± 57 V DC / PoE+) |
| Nominal current IN | ≤ 1.5 A (25 °C) |
| Operating effective current ICat UC | ≤ 600 µA |
| Nominal discharge current In(8/20) µs (line-line) | 350 A |
| Nominal discharge current In(8/20) µs (line-earth) | 350 A |
| Nominal pulse current Ian (10/700) µs (line-line) | ≤ 25 A |
| Nominal pulse current Ian (10/700) µs (line-earth) | ≤ 25 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 25 V |
| ≤ 90 V (PoE) | |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 750 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 25 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 750 V |
| Residual voltage at In(line-line) | ≤ 35 V (C1 - 350 A) |
| ≤ 110 V (C1 - 350 A) | |
| Residual voltage at In(line-earth) | ≤ 700 V (C1 - 350 A) |
| Voltage protection level Up(line-line) | ≤ 20 V (B2 - 1 kV / 25 A) |
| ≤ 90 V (B2 - 1 kV / 25 A - PoE) | |
| ≤ 35 V (C1 - 700 V/350 A) | |
| ≤ 110 V (C1 - 700 V/350 A - PoE) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (B2 - 1 kV / 25 A) |
| ≤ 700 V (C1 - 700 V/350 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | ≤ 1 dB (100 MHz/100 Ω) |
| Near-end crosstalk attenuation | ≤ 63.3 dB (1 MHz/100 Ω) |
| ≤ 43.6 dB (16 MHz/100 Ω) | |
| ≤ 30.1 dB (100 MHz/100 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | > 100 MHz |
| Capacity (line-line) | typ. 15 pF (f= 1 MHz / VR= 0 V) |
| Capacity (line-earth) | typ. 5 pF (f= 1 MHz / VR= 0 V) |
| Impulse durability (line-line) | B2 - 1 kV / 25 A |
| C1 - 700 V / 350 A | |
| Impulse durability (line-earth) | B2 - 1 kV / 25 A |
| C1 - 700 V / 350 A |
Standards and Regulations
| Standards/specifications | IEC 61643-21/A1 2008 |
|---|---|
| GB/T 18802.21 2004 | |
| EN 61643-21/A1 2009 |