View larger
UK 10 N BU 3005086 PHOENIX CONTACT Feed-through terminal block
UK 10 N BU
3005086
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Feed-through terminal block UK 10 N BU by Phoenix Contact is an essential electrical component used within control cabinets to securely join two or more individual wires in a shared electrical circuit. Terminal blocks facilitate clean wire management, reliable current distribution, and safe maintenance access across industrial automation and power distribution panels.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Feed-through terminal block
- Number of connections: 2
- Number of rows: 1
- Potentials: 1
- Data management status Article revision: 17
- Insulation characteristics Overvoltage category: III
- Degree of pollution: 3
- Rated surge voltage: 8 kV
- Maximum power dissipation for nominal condition: 1.82 W
- Number of connections per level: 2
- Nominal cross section: 10 mm²
- Level 1 above 1 below 1 Screw thread: M4
- Tightening torque: 1.5 ... 1.8 Nm
- Stripping length: 10 mm
- Internal cylindrical gage: B6
- Connection in acc. with standard: IEC 60947-7-1
More info
▲| Product type | Feed-through terminal block |
| Number of connections | 2 |
| Number of rows | 1 |
| Potentials | 1 |
| Data management status | |
| Article revision | 17 |
| Insulation characteristics | |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Rated surge voltage | 8 kV |
| Maximum power dissipation for nominal condition | 1.82 W |
| Number of connections per level | 2 |
| Nominal cross section | 10 mm² |
| Level 1 above 1 below 1 | |
| Screw thread | M4 |
| Tightening torque | 1.5 ... 1.8 Nm |
| Stripping length | 10 mm |
| Internal cylindrical gage | B6 |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section rigid | 0.5 mm² ... 16 mm² |
| Cross section AWG | 20 ... 6 (converted acc. to IEC) |
| Conductor cross section flexible | 0.5 mm² ... 10 mm² |
| Conductor cross section, flexible [AWG] | 20 ... 8 (converted acc. to IEC) |
| Conductor cross-section flexible (ferrule without plastic sleeve) | 0.5 mm² ... 10 mm² |
| Flexible conductor cross section (ferrule with plastic sleeve) | 0.5 mm² ... 6 mm² |
| Cross-section with insertion bridge, rigid | 10 mm² |
| Cross-section with insertion bridge, flexible | 10 mm² |
| 2 conductors with same cross section, solid | 0.5 mm² ... 4 mm² |
| 2 conductors with same cross section, flexible | 0.5 mm² ... 4 mm² |
| 2 conductors with same cross section, flexible, with ferrule without plastic sleeve | 0.5 mm² ... 2.5 mm² |
| 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve | 0.5 mm² ... 6 mm² |
| Nominal current | 57 A |
| Maximum load current | 76 A (with 16 mm² conductor cross section) |
| Nominal voltage | 800 V |
| Nominal cross section | 10 mm² |
| Rated data (ATEX/IECEx) | |
| Identification | II 2 GD Ex eb IIC Gb |
| Operating temperature range | -60 °C ... 110 °C |
| Ex-certified accessories | 3003020 D-UK 4/10 |
| 3006027 D-UK 16 | |
| 3004210 ATP-UK 5-MTK | |
| 1205066 SZS 1,0X4,0 VDE | |
| 1201442 E/UK | |
| List of bridges | Fixed bridge / FBI 10-10-EX / 0711690 |
| Bridge data | 51.5 A / 10 mm² |
| List of bridges | Insertion bridge / EB 2-10 / 0203153 |
| Insertion bridge / EB 3-10 / 0203328 | |
| Insertion bridge / EB 10-10 / 0203137 | |
| Bridge data | 50 A / 10 mm² |
| Ex temperature increase | 40 K (59.1 A / 10 mm²) |
| Rated voltage | 690 V |
| at bridging with insertion bridge | 690 V |
| for bridging with bridge | 690 V |
| Rated insulation voltage | 630 V |
| output | (Permanent) |
| Ex level General | |
| Rated current | 53.5 A |
| Maximum load current | 67 A |
| Contact resistance | 0.12 mΩ |
| Ex connection data General | |
| Torque range | 1.5 Nm ... 1.8 Nm |
| Nominal cross section | 10 mm² |
| Rated cross section AWG | 8 |
| Connection capacity rigid | 0.5 mm² ... 16 mm² |
| Connection capacity AWG | 20 ... 6 |
| Connection capacity flexible | 0.5 mm² ... 10 mm² |
| Connection capacity AWG | 20 ... 8 |
| 2 conductors with same cross section, solid | 0.5 mm² ... 4 mm² |
| 2 conductors with the same cross-section AWG rigid | 20 ... 12 |
| 2 conductors with same cross section, stranded | 0.5 mm² ... 4 mm² |
| 2 conductors with the same cross-section AWG flexible | 20 ... 12 |
| Width | 10.2 mm |
| End cover width | 1.8 mm |
| Height | 42.5 mm |
| Depth on NS 32 | 52.3 mm |
| Depth on NS 35/7,5 | 47.3 mm |
| Depth on NS 35/15 | 54.8 mm |
| Color | blue (RAL 5015) |
| Flammability rating according to UL 94 | V0 |
| Insulating material group | I |
| Insulating material | PA |
| Static insulating material application in cold | -60 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Surge voltage test | |
| Test voltage setpoint | 9.8 kV |
| Result | Test passed |
| Temperature-rise test | |
| Requirement temperature-rise test | Increase in temperature ≤ 45 K |
| Result | Test passed |
| Short-time withstand current 10 mm² | 1.2 kA |
| Short-time withstand current 16 mm² | 1.92 kA |
| Result | Test passed |
| Power-frequency withstand voltage | |
| Test voltage setpoint | 2 kV |
| Result | Test passed |
| Mechanical data | |
| Open side panel | Yes |
| Mechanical strength | |
| Result | Test passed |
| Attachment on the carrier | |
| DIN rail/fixing support | NS 32/NS 35 |
| Test force setpoint | 5 N |
| Result | Test passed |
| Test for conductor damage and slackening | |
| Rotation speed | 10 rpm |
| Revolutions | 135 |
| Conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 10 mm² / 2 kg | |
| 16 mm² / 2.9 kg | |
| Result | Test passed |
| Needle-flame test | |
| Time of exposure | 30 s |
| Result | Test passed |
| Ambient conditions | |
| Ambient temperature (operation) | -60 °C ... 110 °C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) |
| Ambient temperature (storage/transport) | -25 °C ... 60 °C (for a short time, no longer than 24 h, -60°C to +70°C) |
| Ambient temperature (assembly) | -5 °C ... 70 °C |
| Ambient temperature (actuation) | -5 °C ... 70 °C |
| Permissible humidity (operation) | 20 % ... 90 % |
| Permissible humidity (storage/transport) | 30 % ... 70 % |
| Connection in acc. with standard | IEC 60947-7-1 |
| Mounting type | NS 35/7,5 |
| NS 35/15 | |
| NS 32 |