View larger
UDK 4-DUR 249 2775249 PHOENIX CONTACT Component terminal block
UDK 4-DUR 249
2775249
PHOENIX CONTACT
50 Pcs.
Automation > Component terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Providing four clamp positions per level, the Phoenix Contact UDK 4-DUR 249 component terminal block functions as an essential distribution hub for complex panel wiring. It allows multiple conductors to interface safely within standard automation infrastructures. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.2 mm²
- Connectable conductor cross section multi-wired (EF007343): 0.2 mm²
- Type of electrical connection 1 (EF002526): Screw connection
- Type of electrical connection 2 (EF002527): Screw connection
- Number of levels (EF002659): 1
- Number of clamp positions per level (EF002660): 4
- Internally connected stages (EF002661): Yes
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Width (EF000008): 6.2 mm
- Height (EF000040): 63.5 mm
- Depth (EF000049): 47 mm
- Closing plate required (EF002525): Yes
- Colour (EF000007): Grey
More info
▲Key Commercial Data
| Orderkey | 2775249 |
|---|---|
| Packing unit | 50 pc |
| Catalog page | Page 494 (C-1-2017) |
| GTIN | 4017918068530 |
| Weight per Piece (excluding packing) | 15.780 g |
| Custom tariff number | 85369010 |
| Country of origin | PL (Poland) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 4 |
| Nominal cross section | 4 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Maximum load current | the current is determined by the component used |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Connection in acc. with standard | IEC 60947-7-1 |
| Nominal current IN | 32 A (the current is determined by the component used) |
| Nominal voltage UN | 630 V |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 3 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test conductor cross section/weight | 0.2 mm² / 0.2 kg |
| 4 mm² / 0.9 kg | |
| 6 mm2/ 1.4 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.2 mm² |
| Tractive force setpoint | 10 N |
| Conductor cross section tensile test | 4 mm² |
| Tractive force setpoint | 60 N |
| Conductor cross section tensile test | 6 mm² |
| Tractive force setpoint | 80 N |
| Result of tight fit on support | Test passed |
| Setpoint | 1 N |
| Result of voltage-drop test | Test passed |
| Result of temperature-rise test | Test passed |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.25 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 1.5 mm² |
| 2 conductors with same cross section, solid min. | 0.2 mm² |
| 2 conductors with same cross section, solid max. | 1 mm² |
| 2 conductors with same cross section, stranded min. | 0.2 mm² |
| 2 conductors with same cross section, stranded max. | 1.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.25 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 1.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 1 mm² |
| Cross section with insertion bridge, solid max. | 2.5 mm² |
| Cross section with insertion bridge, stranded max. | 2.5 mm² |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Internal cylindrical gage | A4 |
| Screw thread | M3 |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V2 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |