PHOENIX CONTACT STU 10/ 4X2,5 STU 10/ 4X2,5 3033139 PHOENIX CONTACT Potential collective terminal View larger
Images are for illustrative purposes only. Please refer to data sheet for details

STU 10/ 4X2,5 3033139 PHOENIX CONTACT Potential collective terminal

STU 10/ 4X2,5

3033139

PHOENIX CONTACT

50 Pcs.

Potential collective terminal Collective potential terminal, nominal voltage: 800 V, nominal current: 55 A, number of connections: 5, connection type: Screw connection, Sizing cross-section: 10 mm², cross-section: 0.5 mm² - 16 mm², Spring connection, Sizing cross-section: 2.5 mm², cross-section: 0.08 mm² - 4 mm², mounting class: NS 35/7.5, NS 35/15, color: gray

Automation > Feed-through terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact STU 10/ 4X2,5 is a potential collective terminal combining screw and spring clamp connections to distribute power across varying cable cross-sections in heavy-duty control panels. Such terminal blocks simplify main power feed integration and branch circuit wiring.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Rated current In (EF008250): 55 A
  • Rated voltage (EF000228): 800 V
  • Type of electrical connection 1 (EF002526): Screw connection
  • Type of electrical connection 2 (EF002527): Spring clamp connection
  • Number of levels (EF002659): 1
  • Number of clamp positions per level (EF002660): 5
  • Suitable for conductor material (EF012572): Aluminium/copper
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 10.3 mm
  • Height (EF000040): 68 mm
  • Depth (EF000049): 48.3 mm
  • Closing plate required (EF002525): Yes
  • Colour (EF000007): Grey
  • Internally connected stages (EF002661): Yes

More info

▲

Key Commercial Data

Orderkey3033139
Packing unit50 pc
Minimum order quantity50 pc
Catalog pagePage 190 (C-1-2017)
GTIN4046356148030
Weight per Piece (excluding packing)20.700 g
Custom tariff number85369010
Country of originPL (Poland)

General

Number of levels1
Number of connections5
Nominal cross section10 mm²
Colorgray
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage8 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition1.82 W
Connection methodScrew connection
Connection in acc. with standardIEC 60947-7-1
Maximum load current57 A
Nominal current IN55 A
Nominal voltage UN800 V
Connection methodSpring-cage connection
Connection in acc. with standardIEC 60947-7-1
Maximum load current24 A
Nominal current IN24 A
Nominal voltage UN800 V
Open side panelYes
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint9.8 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint2 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.08 mm² / 0.1 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
0.5 mm² / 0.3 kg
10 mm² / 2 kg
16 mm² / 2.9 kg
Tensile test resultTest passed
Conductor cross section tensile test0.08 mm²
Tractive force setpoint5 N
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Conductor cross section tensile test4 mm²
Tractive force setpoint60 N
Conductor cross section tensile test0.5 mm²
Tractive force setpoint20 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint5 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 1.6 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Conductor cross section short circuit testing4 mm²
Short-time current0.48 kA
Result of aging testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width10.3 mm
Length68 mm
Height NS 35/7,548.3 mm
Height NS 35/1555.8 mm
End cover width2.2 mm

Connection data

Connection methodScrew connection
Connection in acc. with standardIEC 60947-7-1
Screw threadM4
Tightening torque, min1.5 Nm
Tightening torque max1.8 Nm
Stripping length8 mm ... 10 mm
Conductor cross section solid min.0.5 mm²
Conductor cross section solid max.16 mm²
Conductor cross section AWG min.20
Conductor cross section AWG max.6
Conductor cross section flexible min.0.5 mm²
Conductor cross section flexible max.16 mm²
Min. AWG conductor cross section, flexible20
Max. AWG conductor cross section, flexible6
Conductor cross section flexible, with ferrule without plastic sleeve min.0.5 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.10 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.10 mm²
2 conductors with same cross section, solid min.0.5 mm²
2 conductors with same cross section, solid max.4 mm²
2 conductors with same cross section, stranded min.0.5 mm²
2 conductors with same cross section, stranded max.4 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, ferrules without plastic sleeve, max.2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.6 mm²
Internal cylindrical gageA6
Connection methodSpring-cage connection
Connection in acc. with standardIEC 60947-7-1
Stripping length8 mm ... 10 mm
Conductor cross section solid min.0.08 mm²
Conductor cross section solid max.4 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.10
Conductor cross section flexible min.0.08 mm²
Conductor cross section flexible max.2.5 mm²
Min. AWG conductor cross section, flexible24
Max. AWG conductor cross section, flexible12
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min.0.14 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.0.5 mm²

Standards and Regulations

Connection in acc. with standardCUL
IEC 60947-7-1
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet