View larger
STTB 4-PE 3036039 PHOENIX CONTACT Protective conductor double-level terminal block, Cross section: 0.08 mm²
STTB 4-PE
3036039
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built as a protective conductor double-level terminal block, the Phoenix Contact STTB 4-PE provides safe earthing and signal distribution within control cabinets. Industrial wiring setups rely on these grounding blocks to route protective earth paths efficiently alongside standard circuits. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Connectable conductor cross section solid-core (EF007337): 0.08 mm²
- Type of electrical connection 1 (EF002526): Spring clamp connection
- Type of electrical connection 2 (EF002527): Spring clamp connection
- Number of levels (EF002659): 2
- Number of clamp positions per level (EF002660): 2
- Suitable for conductor material (EF012572): Aluminium/copper
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Width (EF000008): 6.2 mm
- Height (EF000040): 83.5 mm
- Depth (EF000049): 47.5 mm
- Explosion-tested version 'Ex e' (EF008498): Yes
- Closing plate required (EF002525): Yes
- Colour (EF000007): Green/yellow
- Internally connected stages (EF002661): No
More info
▲General
| Number of levels | 2 |
|---|---|
| Number of connections | 4 |
| Nominal cross section | 4 mm² |
| Color | green-yellow |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Area of application | Railway industry |
| Mechanical engineering | |
| Plant engineering | |
| Process industry |
General
| Rated surge voltage | 6 kV |
|---|---|
| Pollution degree | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Connection in acc. with standard | IEC 60947-7-2 |
| Open side panel | ja |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 2, bogie mounted |
| Test frequency | f1= 5 Hz to f2= 250 Hz |
| ASD level | 6.12 (m/s2)2/Hz |
| Acceleration | 3.12 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 30g |
| Shock duration | 18 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec.; UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -60 °C |
Dimensions
| Width | 6.2 mm |
|---|---|
| Length | 83.5 mm |
| Height NS 35/7,5 | 47.5 mm |
| Height NS 35/15 | 55 mm |
Connection data
| Note | Please observe the current carrying capacity of the DIN rails. |
|---|---|
| Connection method | Spring-cage connection |
| Conductor cross section solid min. | 0.08 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.08 mm² |
| Conductor cross section flexible max. | 4 mm² |
| Conductor cross section AWG min. | 28 |
| Conductor cross section AWG max. | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 4 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.14 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 1 mm² |
| Minimum stripping length | 8 mm |
| Maximum stripping length | 10 mm |
| Internal cylindrical gage | A4 |