Double-level terminal block Double-deck terminal block, with potential splicers, nominal voltage: 500 V, nominal current: 22 A, number of connections: 4, connection type: Spring connection, 1st and 2nd floor, Sizing cross-section: 2.5 mm², cross-section: 0.08 mm² - 4 mm², mounting class: NS 35/7.5, NS 35/15, color: blue

Automation > Feed-through terminal block
Modular TBs

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

An STTB 2,5-PV BU 3035108 PHOENIX CONTACT Double-level terminal block provides dual connection tiers within a single housing footprint, optimizing space in dense control system designs. Multi-level terminal blocks allow high-density signal management and wire organization.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Connectable conductor cross section solid-core (EF007337): 0.08 mm²
  • Rated current In (EF008250): 22 A
  • Rated voltage (EF000228): 500 V
  • Type of electrical connection 1 (EF002526): Spring clamp connection
  • Type of electrical connection 2 (EF002527): Spring clamp connection
  • Number of levels (EF002659): 2
  • Number of clamp positions per level (EF002660): 2
  • Suitable for conductor material (EF012572): Aluminium/copper
  • Mounting method (EF000003): DIN rail (top hat rail) 35 mm
  • Width (EF000008): 5.2 mm
  • Height (EF000040): 67.5 mm
  • Depth (EF000049): 47.5 mm
  • Explosion-tested version 'Ex e' (EF008498): Yes
  • Closing plate required (EF002525): Yes
  • Colour (EF000007): Blue
  • Internally connected stages (EF002661): Yes

More info

▲

Key Commercial Data

Orderkey3035108
Packing unit50 pc
Minimum order quantity50 pc
Catalog pagePage 158 (C-1-2017)
GTIN4017918975258
Weight per Piece (excluding packing)10.300 g
Custom tariff number85369010
Country of originDE (Germany)

General

Number of levels2
Number of connections4
Nominal cross section2.5 mm²
Colorblue
Insulating materialPA
Flammability rating according to UL 94V0
Rated surge voltage6 kV
Degree of pollution3
Overvoltage categoryIII
Insulating material groupI
Maximum power dissipation for nominal condition0.77 W (the value is multiplied when connecting multiple levels)
Connection in acc. with standardIEC 60947-7-1
Nominal current IN22 A (with 4 mm² conductor cross section)
Maximum load current26 A (in case of a 4 mm² conductor cross section, the maximum load current must not be exceeded by the total current of all connected conductors.)
Nominal voltage UN500 V
Open side panelYes
Shock protection test specificationDIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protectionguaranteed
Finger protectionguaranteed
Result of surge voltage testTest passed
Surge voltage test setpoint7.3 kV
Result of power-frequency withstand voltage testTest passed
Power frequency withstand voltage setpoint1.89 kV
Checking the mechanical stability of terminal points (5 x conductor connection)Test passed
Result of bending testTest passed
Bending test rotation speed10 rpm
Bending test turns135
Bending test conductor cross section/weight0.08 mm² / 0.1 kg
2.5 mm² / 0.7 kg
4 mm² / 0.9 kg
Tensile test resultTest passed
Conductor cross section tensile test0.08 mm²
Tractive force setpoint5 N
Conductor cross section tensile test2.5 mm²
Tractive force setpoint50 N
Conductor cross section tensile test4 mm²
Tractive force setpoint60 N
Result of tight fit on supportTest passed
Tight fit on carrierNS 35
Setpoint1 N
Result of voltage-drop testTest passed
Requirements, voltage drop≤ 3.2 mV
Result of temperature-rise testTest passed
Short circuit stability resultTest passed
Conductor cross section short circuit testing2.5 mm²
Short-time current0.3 kA
Conductor cross section short circuit testing4 mm²
Short-time current0.48 kA
Result of aging testTest passed
Ageing test for screwless modular terminal block temperature cycles192
Result of thermal testTest passed
Proof of thermal characteristics (needle flame) effective duration30 s
Oscillation, broadband noise test resultTest passed
Test specification, oscillation, broadband noiseDIN EN 50155 (VDE 0115-200):2008-03
Test spectrumService life test category 2, bogie-mounted
Test frequencyf1= 5 Hz to f2= 250 Hz
ASD level6.12 (m/s2)2/Hz
Acceleration3.12 g
Test duration per axis5 h
Test directionsX-, Y- and Z-axis
Shock test resultTest passed
Test specification, shock testDIN EN 50155 (VDE 0115-200):2008-03
Shock formHalf-sine
Acceleration30g
Shock duration18 ms
Number of shocks per direction3
Test directionsX-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec.; UL 746 B)130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))125 °C
Static insulating material application in cold-60 °C
Behavior in fire for rail vehicles (DIN 5510-2)Test passed
Flame test method (DIN EN 60695-11-10)V0
Oxygen index (DIN EN ISO 4589-2)>32 %
NF F16-101, NF F10-102 Class I2
NF F16-101, NF F10-102 Class F2
Surface flammability NFPA 130 (ASTM E 162)passed
Specific optical density of smoke NFPA 130 (ASTM E 662)passed
Smoke gas toxicity NFPA 130 (SMP 800C)passed
Calorimetric heat release NFPA 130 (ASTM E 1354)27,5 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Dimensions

Width5.2 mm
Length67.5 mm
Height NS 35/7,547.5 mm
Height NS 35/1555 mm

Connection data

Connection methodSpring-cage connection
Conductor cross section solid min.0.08 mm²
Conductor cross section solid max.4 mm²
Conductor cross section flexible min.0.08 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.28
Conductor cross section AWG max.12
Conductor cross section flexible, with ferrule without plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max.2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min.0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max.2.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max.0.5 mm²
Stripping length8 mm ... 10 mm
Internal cylindrical gageA3

Standards and Regulations

Connection in acc. with standardCSA
IEC 60947-7-1
Flammability rating according to UL 94V0
Fire protection for rail vehicles (DIN EN 45545-2) R22HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26HL 1 - HL 3

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.