View larger
SSK 110 KER-EX 0502058 PHOENIX CONTACT Feed-through terminal block
SSK 110 KER-EX
0502058
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Constructed with ceramic insulation, the Phoenix Contact SSK 110 KER-EX feed-through terminal block withstands high-temperature operating conditions. Ceramic terminal blocks are deployed in extreme industrial environments where standard plastics are inadequate. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 0502058
- Packing unit: 50 pc
- Minimum order quantity: 50 pc
- Catalog page: Page 512 (C-1-2017)
- GTIN: 4017918002510
- Weight per Piece (excluding packing): 26.080 g
- Custom tariff number: 85369010
- Country of origin: DE (Germany)
- Number of levels: 1
- Number of connections: 2
- Potentials: 1
- Nominal cross section: 6 mm²
- Color: ivory
- Insulating material: PA
- Material: Ceramics
- Flammability rating according to UL 94: V0
More info
▲Key Commercial Data
| Orderkey | 0502058 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Catalog page | Page 512 (C-1-2017) |
| GTIN | 4017918002510 |
| Weight per Piece (excluding packing) | 26.080 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Potentials | 1 |
| Nominal cross section | 6 mm² |
| Color | ivory |
| Insulating material | PA |
| Material | Ceramics |
| Flammability rating according to UL 94 | V0 |
| Maximum load current | 57 A (with 10 mm² conductor cross section) |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.31 W |
| Maximum load current | 57 A (with 10 mm² conductor cross section) |
| Nominal current IN | 41 A |
| Nominal voltage UN | 800 V |
| Open side panel | Yes |
| Shock protection test specification | IEC 60529:2001-02 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 6 mm2/ 1.4 kg | |
| 10 mm² / 2 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.5 mm² |
| Tractive force setpoint | 20 N |
| Conductor cross section tensile test | 6 mm² |
| Tractive force setpoint | 80 N |
| Conductor cross section tensile test | 10 mm² |
| Tractive force setpoint | 90 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 6 mm² |
| Short-time current | 0.72 kA |
| Conductor cross section short circuit testing | 10 mm² |
| Short-time current | 1.2 kA |
| Relative insulation material temperature index (Elec., UL 746 B) | 1000 °C |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 8 |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 20 |
| Max. AWG conductor cross section, flexible | 10 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 6 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| 2 conductors with same cross section, solid min. | 0.5 mm² |
| 2 conductors with same cross section, solid max. | 2.5 mm² |
| 2 conductors with same cross section, stranded min. | 0.5 mm² |
| 2 conductors with same cross section, stranded max. | 2.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 2.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 2.5 mm² |
| Connection in acc. with standard | IEC/EN 60079-7 |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 8 |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 20 |
| Max. AWG conductor cross section, flexible | 10 |
| Stripping length | 10 mm |
| Internal cylindrical gage | A4 |
| Screw thread | M4 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CSA |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |