A Phoenix Contact RTO 5 BU bolt connection terminal block allows secure cable termination in heavy-duty electrical installations. Terminal blocks are commonly utilized within switchgear assemblies to distribute power safely and ensure reliable interconnections between different system components. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated current In (EF008250): 41 A
- Rated voltage (EF000228): 1000 V
- Type of electrical connection 1 (EF002526): Bolt connection
- Type of electrical connection 2 (EF002527): Bolt connection
- Number of clamp positions per level (EF002660): 2
- Suitable for conductor material (EF012572): Aluminium/copper
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Operating temperature (EF002393): -60 °C
- Width (EF000008): 16.3 mm
- Height (EF000040): 66 mm
- Depth (EF000049): 49.9 mm
- Closing plate required (EF002525): Yes
- Colour (EF000007): Blue
- Internally connected stages (EF002661): Yes
More info
▲Key Commercial Data
| Orderkey | 3049767 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 379 (C-1-2017) |
| GTIN | 4046356283564 |
| Weight per Piece (excluding packing) | 27.870 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
General
| Note | Note: the BE-RT... path extension is to be used for non-insulated cable lugs (see accessories). |
|---|---|
| Number of levels | 1 |
| Number of connections | 2 |
| Potentials | 1 |
| Nominal cross section | 6 mm² |
| Color | blue |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.31 W |
| Maximum load current | 41 A (with 6 mm² conductor cross section) |
| Nominal current IN | 41 A |
| Nominal voltage UN | 1000 V |
| Open side panel | Yes |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2.2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 6 mm² |
| Short-time current | 0.72 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Note | Connection bolts |
|---|---|
| Connection method | Bolt connection |
| Screw thread | M5 |
| Tightening torque, min | 2.5 Nm |
| Tightening torque max | 3 Nm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section solid min. | 0.5 mm² |
| Conductor cross section solid max. | 6 mm² |
| Conductor cross section flexible min. | 0.1 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Min. AWG conductor cross section, flexible | 26 |
| Max. AWG conductor cross section, flexible | 10 |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.1 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 6 mm² |
| Cable lug connection according to standard | DIN 46234 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 6 mm² |
| Hole diameter, min. | 5.3 mm |
| Cable lug width, max. | 10 mm |
| Bolt diameter | 5 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 1 mm² |
| Max. cross section for cable lug connection | 6 mm² |
| Hole diameter, min. | 5.3 mm |
| Cable lug width, max. | 10 mm |
| Bolt diameter | 5 mm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |