View larger
RT 3 3049013 PHOENIX CONTACT Bolt connection terminal block
RT 3
3049013
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Utilizing robust threaded hardware for secure fastening, the Phoenix Contact RT 3 bolt connection terminal block handles high-stress industrial electrical connections. Bolt connection blocks are commonly chosen for heavy-duty power distribution and machinery wiring where mechanical stability is paramount. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Rated current In (EF008250): 24 A
- Rated voltage (EF000228): 1000 V
- Type of electrical connection 1 (EF002526): Bolt connection
- Type of electrical connection 2 (EF002527): Bolt connection
- Number of clamp positions per level (EF002660): 2
- Suitable for conductor material (EF012572): Aluminium/copper
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Operating temperature (EF002393): -60 °C
- Width (EF000008): 12.3 mm
- Height (EF000040): 66 mm
- Depth (EF000049): 51 mm
- Closing plate required (EF002525): Yes
- Colour (EF000007): Grey
- Internally connected stages (EF002661): Yes
More info
▲Key Commercial Data
| Orderkey | 3049013 |
|---|---|
| Packing unit | 50 pc |
| Minimum order quantity | 50 pc |
| Catalog page | Page 377 (C-1-2017) |
| GTIN | 4046356140140 |
| Weight per Piece (excluding packing) | 25.880 g |
| Custom tariff number | 85369010 |
| Country of origin | CN (China) |
General
| Note | Note: the BE-RT... path extension is to be used for non-insulated cable lugs (see accessories). |
|---|---|
| Number of levels | 1 |
| Number of connections | 2 |
| Potentials | 1 |
| Nominal cross section | 2.5 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Area of application | Railway industry |
| Machine building | |
| Plant engineering | |
| Process industry | |
| Rated surge voltage | 8 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 0.77 W |
| Maximum load current | 24 A (with a 2.5 mm² conductor cross section) |
| Nominal current IN | 24 A |
| Nominal voltage UN | 1000 V (Rated voltage for open disconnect point 500 V) |
| Open side panel | Yes |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Note regarding shock protection | Electric shock protection only with insulated cable lug and closed wing flap guaranteed. |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 9.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 2.2 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 35 |
| Setpoint | 1 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 2.5 mm² |
| Short-time current | 0.3 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 1, class B, body mounted |
| Test frequency | f1= 5 Hz to f2= 150 Hz |
| ASD level | 1.857 (m/s2)2/Hz |
| Acceleration | 0,8 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 5 g |
| Shock duration | 30 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 130 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 28 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Note | Connection bolts |
|---|---|
| Connection method | Bolt connection |
| Screw thread | M3 |
| Tightening torque, min | 0.6 Nm |
| Tightening torque max | 0.8 Nm |
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section flexible min. | 0.1 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Min. AWG conductor cross section, flexible | 26 |
| Max. AWG conductor cross section, flexible | 14 |
| Cable lug connection according to standard | DIN 46234 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter, min. | 3.2 mm |
| Cable lug width, max. | 6 mm |
| Bolt diameter | 3 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 1 mm² |
| Max. cross section for cable lug connection | 2.5 mm² |
| Hole diameter, min. | 3.2 mm |
| Cable lug width, max. | 6 mm |
| Bolt diameter | 3 mm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |