Loop-powered field displays like the FA MCR-FDS-I-I-OLP 2908782 PHOENIX CONTACT Digital display produced by Phoenix Contact offer clear measurement visualization directly within industrial measurement circuits without requiring auxiliary power. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2908782
- Packing unit: 1 pc
- Catalog page: Page 183 (C-5-2017)
- GTIN: 4055626357096
- Weight per Piece (excluding packing): 0.000 g
- Custom tariff number: 90328900
- Country of origin: DE (Germany)
- Width: 131 mm
- Height: 81.5 mm
- Depth: 55.5 mm
- Ambient temperature (operation): -40 °C ... 60 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Maximum altitude: < 5000 m (Above sea level)
- Description of the input: Current measuring input
- Current input signal: 4 mA ... 20 mA
- Max. input current: 200 mA
More info
▲Key Commercial Data
| Orderkey | 2908782 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 183 (C-5-2017) |
| GTIN | 4055626357096 |
| Weight per Piece (excluding packing) | 0.000 g |
| Custom tariff number | 90328900 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | < 5000 m (Above sea level) |
Input data
| Description of the input | Current measuring input |
|---|---|
| Current input signal | 4 mA ... 20 mA |
| Max. input current | 200 mA |
| Description of the input | HART |
| Current input signal | up to 4x HART signals |
General
| Maximum transmission error | 0.1 % (of final value) |
|---|---|
| Maximum temperature coefficient | < 0.02 %/K |
| Noise emission | IEC 61326, class B |
| Housing material | Aluminum |
| Mounting position | Max. viewing angle range +/- 45° from the centre line of the display in every direction |
| Conformance | CE-compliant |
| UL, USA/Canada | UL 61010 Listed |
Standards and Regulations
| Noise emission | IEC 61326, class B |
|---|---|
| Conformance | CE-compliant |
| UL, USA/Canada | UL 61010 Listed |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | B |
| DNV GL-Enclosure | - (panel housing IP65 at front, IP20 at rear, Field housing IP67) |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |