PHOENIX CONTACT FA MCR-FDS-I-I-OLP FA MCR-FDS-I-I-OLP 2908782 PHOENIX CONTACT Digital display View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FA MCR-FDS-I-I-OLP 2908782 PHOENIX CONTACT Digital display

FA MCR-FDS-I-I-OLP

2908782

PHOENIX CONTACT

1 Pcs.

Digital display Output loop-fed process indicator in field box. HART

Automation > Accessories/spare parts for HVAC sensors
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Loop-powered field displays like the FA MCR-FDS-I-I-OLP 2908782 PHOENIX CONTACT Digital display produced by Phoenix Contact offer clear measurement visualization directly within industrial measurement circuits without requiring auxiliary power. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2908782
  • Packing unit: 1 pc
  • Catalog page: Page 183 (C-5-2017)
  • GTIN: 4055626357096
  • Weight per Piece (excluding packing): 0.000 g
  • Custom tariff number: 90328900
  • Country of origin: DE (Germany)
  • Width: 131 mm
  • Height: 81.5 mm
  • Depth: 55.5 mm
  • Ambient temperature (operation): -40 °C ... 60 °C
  • Ambient temperature (storage/transport): -40 °C ... 85 °C
  • Maximum altitude: < 5000 m (Above sea level)
  • Description of the input: Current measuring input
  • Current input signal: 4 mA ... 20 mA
  • Max. input current: 200 mA

More info

Key Commercial Data

Orderkey2908782
Packing unit1 pc
Catalog pagePage 183 (C-5-2017)
GTIN4055626357096
Weight per Piece (excluding packing)0.000 g
Custom tariff number90328900
Country of originDE (Germany)

Dimensions

Width131 mm
Height81.5 mm
Depth55.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 60 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Maximum altitude< 5000 m (Above sea level)

Input data

Description of the inputCurrent measuring input
Current input signal4 mA ... 20 mA
Max. input current200 mA
Description of the inputHART
Current input signalup to 4x HART signals

Output data

Output nameCurrent output
Current output signal4 mA ... 20 mA

Power supply

Supply voltage rangeloop-powered, no external supply necessary

General

Maximum transmission error0.1 % (of final value)
Maximum temperature coefficient< 0.02 %/K
Noise emissionIEC 61326, class B
Housing materialAluminum
Mounting positionMax. viewing angle range +/- 45° from the centre line of the display in every direction
ConformanceCE-compliant
UL, USA/CanadaUL 61010 Listed

Standards and Regulations

Noise emissionIEC 61326, class B
ConformanceCE-compliant
UL, USA/CanadaUL 61010 Listed
DNV GL-TemperatureB
DNV GL-HumidityB
DNV GL-VibrationA
DNV GL-EMCB
DNV GL-Enclosure- (panel housing IP65 at front, IP20 at rear, Field housing IP67)

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.