View larger
MACX MCR-EX-SL-SD-21-60-LP 2865515 PHOENIX CONTACT Solenoid driver
MACX MCR-EX-SL-SD-21-60-LP
2865515
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MACX MCR-EX-SL-SD-21-60-LP 2865515 PHOENIX CONTACT Solenoid driver provides intrinsically safe power distribution and signal routing for controlling explosion-protected actuators. Solenoid drivers are extensively deployed within chemical, oil, and gas facilities to isolate control systems from hazardous field elements. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
- Number of input ranges 0 V ... 1 V (EF006890): 0
More info
▲Key Commercial Data
| Orderkey | 2865515 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 163 (C-5-2017) |
| GTIN | 4046356160575 |
| Weight per Piece (excluding packing) | 120.800 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C (any mounting position, pay attention to the derating curve in the data sheet) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 |
Output data
| Output characteristic curve: Output resistor | 133.4 Ω (Internal resistance Ri) |
|---|---|
| Response time | 20 ms |
Compatible valves
| Note | This is an extract of possible combinations of valves and solenoid drivers. |
|---|---|
| Compatible valve | ASCO Coil 302 (12 V) |
| ASCO Coil 302 (24 V) | |
| Bürkert Coil AC 10 standard | |
| Bürkert Coil AC 10 high resistance | |
| FESTO Coil MFH-...IA-SA-EX GBXE022AIAD03 | |
| FESTO Coil (J)MFH-...BIA-SA-EX GBXE022AIAD03 | |
| Norgren Herion Coil 2050 | |
| Norgren Herion Coil 2051 | |
| Norgren Herion Coil 2052 | |
| Norgren Herion Coil 2053 | |
| Parker Coil VZ95 482160.01 EEx ia IIB T6 |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
General
| No. of channels | 1 |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Status display | Yellow LED (switching state / status, lights up when output circuit is active) |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Output/input |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) | |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIB Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIB Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| SIL | 3 |
Safety characteristic data
| Integrity requirement | IEC 61508 - Low demand |
|---|---|
| Equipment type | Type A |
| Safety Integrity Level (SIL) | 3 |
| Safe Failure Fraction (SFF) | 100 % |
| λSU | 2.84 x 10-7(284 FIT) |
| λSD | 0 |
| λDU | 0 |
| λDD | 0 |
| Probability of a hazardous failure on demand (PFDAVG) | 0 (1 year) |
| 0 (5 years) | |
| 0 (10 years) | |
| Diagnostic coverage (DC) | DCS=0 %, DCD=0 % |
Safety data
| Input power Pi | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 25.1 V |
| Max. output current Io | 188 mA |
| Max. output power Po | 1.18 W |
| Group | IIB |
| Max. external inductivity Lo | 4 mH |
| Max. external capacity Co | 0.83 µF |
| Group | IIA |
| Max. external inductivity Lo | 7.5 mH |
| Max. external capacity Co | 2.93 µF |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIB Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIB Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIB |
| IIA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |