View larger
MACX MCR-EX-SL-SD-21-25-LP 2865492 PHOENIX CONTACT Solenoid driver
MACX MCR-EX-SL-SD-21-25-LP
2865492
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The MACX MCR-EX-SL-SD-21-25-LP 2865492 PHOENIX CONTACT Solenoid driver acts as an intrinsically safe interface module for safely driving field control devices in explosive environments. Solenoid drivers restrict electrical energy transferred into hazardous zones, ensuring compliance with strict industrial safety standards.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
- Number of input ranges 0 V ... 1 V (EF006890): 0
More info
▲Key Commercial Data
| Orderkey | 2865492 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 162 (C-5-2017) |
| GTIN | 4046356160551 |
| Weight per Piece (excluding packing) | 147.500 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 |
Output data
| Output characteristic curve: Output resistor | 641.1 Ω (Internal resistance Ri) |
|---|---|
| Response time | 20 ms |
Compatible valves
| Note | This is an extract of possible combinations of valves and solenoid drivers. |
|---|---|
| Compatible valve | Norgren Herion Coil 2080 / 2082 |
| Norgren Herion Coil 2081 / 2083 | |
| Norgren Herion Coil 2084 | |
| Hörbiger Piezo P8 38x RF-Nx-SPN65 30 V type | |
| Hörbiger Piezo P20 381RF-NG-CPN61 30 V type | |
| Samson Coil 3701-11 (6 V) | |
| Samson Coil 3701-12 (12 V) | |
| Samson Coil 3701-13 (24 V) | |
| Samson Coil 3963-11 (6 V) | |
| Samson Coil 3963-12 (12 V) | |
| Samson Coil 3963-13 (24 V) | |
| Samson Coil 3964-11 (6 V) | |
| Samson Coil 3964-12 (12 V) | |
| Samson Coil 3964-13 (24 V) | |
| Seitz Pilot valve PV 12F73 Ci oH | |
| Seitz Pilot valve PV 12F73 Xi oH | |
| Seitz Pilot valve PV 12F73 Xi oH-2 |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 14 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Connection method | Screw connection |
| Tightening torque, min | 0.5 Nm |
| Tightening torque max | 0.6 Nm |
General
| No. of channels | 1 |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Status display | Yellow LED (switching state / status, lights up when output circuit is active) |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Output/input |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) | |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC/IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIC Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC/IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIC Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| SIL | 3 |
Safety characteristic data
| Integrity requirement | IEC 61508 - Low demand |
|---|---|
| Equipment type | Type A |
| Safety Integrity Level (SIL) | 3 |
| Safe Failure Fraction (SFF) | 100 % |
| λSU | 2.84 x 10-7(284 FIT) |
| λSD | 0 |
| λDU | 0 |
| λDD | 0 |
| Probability of a hazardous failure on demand (PFDAVG) | 0 (1 year) |
| 0 (5 years) | |
| 0 (10 years) | |
| Diagnostic coverage (DC) | DCS=0 %, DCD=0 % |
Safety data
| Input power Pi | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 25.1 V |
| Max. output current Io | 39 mA |
| Max. output power Po | 245 mW |
| Group | IIC |
| Max. external inductivity Lo | 22 mH |
| Max. external capacity Co | 0.108 µF |
| Group | IIB |
| Max. external inductivity Lo | 90 mH |
| Max. external capacity Co | 0.83 µF |
| Group | IIA |
| Max. external inductivity Lo | 170 mH |
| Max. external capacity Co | 2.93 µF |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC/IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIC Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC/IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIC Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIB | |
| IIA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |