View larger
MACX MCR-EX-SL-SD-24-48-LP-SP 2924126 PHOENIX CONTACT Solenoid driver
MACX MCR-EX-SL-SD-24-48-LP-SP
2924126
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact MACX MCR-EX-SL-SD-24-48-LP-SP solenoid driver safely energizes field valves and actuators installed within hazardous explosion-risk zones. Loop-powered isolation barriers restrict electrical energy thresholds to maintain safety compliance across industrial process control loops.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
- Number of input ranges 0 V ... 1 V (EF006890): 0
More info
▲Key Commercial Data
| Orderkey | 2924126 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 163 (C-5-2017) |
| GTIN | 4046356338486 |
| Weight per Piece (excluding packing) | 145.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C (any mounting position, pay attention to the derating curve in the data sheet) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 |
Output data
| Minimum output voltage | 10.5 V DC (At 48 mA) |
|---|---|
| Output characteristic curve: Output resistor | 275.7 Ω (Internal resistance Ri) |
| Response time | 20 ms |
Compatible valves
| Note | This is an extract of possible combinations of valves and solenoid drivers. |
|---|---|
| Compatible valve | ASCO Coil 195 |
| ASCO Coil 302 (12 V) | |
| Bürkert Coil AC 10 standard | |
| Bürkert Coil AC 10 high resistance | |
| Bürkert Coil AC 21 standard 700 mW / 65°C | |
| Bürkert Coil AC 21 high resistance 700 mW / 65°C | |
| Bürkert Coil AC 21 standard 900 mW / 45°C | |
| Bürkert Coil AC 21 high resistance 900 mW / 45°C | |
| Bürkert Coil AC 21 standard 900 mW / 60°C | |
| Bürkert Coil AC 21 high resistance 900 mW / 60°C | |
| Bürkert Coil G1 642735 standard 800 mW / 40°C | |
| Bürkert Coil G1 642735 high resistance 800 mW / 40°C | |
| Bürkert Coil G1 642735 standard 1000 mW / 40°C | |
| Bürkert Coil G1 642735 high resistance 1000 mW / 40°C | |
| FESTO Coil MFH-...IA-SA-EX GBXE022AIAD03 | |
| FESTO Coil (J)MFH-...BIA-SA-EX GBXE022AIAD03 | |
| Norgren Herion Coil 2050 | |
| Norgren Herion Coil 2051 | |
| Norgren Herion Coil 2052 | |
| Norgren Herion Coil 2053 | |
| Norgren Herion Coil 2080 / 2082 | |
| Norgren Herion Coil 2081 / 2083 | |
| Norgren Herion Coil 2084 | |
| Norgren Herion Coil 3039 | |
| Nass Coil 1259 30.1-00 | |
| Nass Coil 1259 50.1-00 | |
| Parker Coil VZ07 488650.01 | |
| Parker Coil VZ33 494035.10 | |
| Parker Coil VZ08 488660.01 | |
| Parker Coil VZ09 488670.01 | |
| Parker Coil VZ95 482160.01 EEx ia IIB T6 | |
| Parker Coil VZ23 482870.01 | |
| Samson Coil 3701-12 (12 V) | |
| Samson Coil 3701-13 (24 V) | |
| Samson Coil 3963-12 (12 V) | |
| Samson Coil 3963-13 (24 V) | |
| Samson Coil 3964-12 (12 V) | |
| Samson Coil 3964-13 (24 V) | |
| Seitz Pilot valve PV 12F73 Ci oH | |
| Seitz Pilot valve PV 12F73 Xi oH | |
| Seitz Pilot valve PV 12F73 Xi oH-2 | |
| Seitz Solenoid coil 11 G 52 |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
General
| No. of channels | 1 |
|---|---|
| Maximum temperature coefficient | 0.01 %/K |
| Status display | Yellow LED (switching state / status, lights up when output circuit is active) |
| Flammability rating according to UL 94 | V0 |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Output/input |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) | |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC/IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIC Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC/IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIC Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| SIL | 3 |
Safety characteristic data
| Integrity requirement | IEC 61508 - Low demand |
|---|---|
| Equipment type | Type A |
| Safety Integrity Level (SIL) | 3 |
| Safe Failure Fraction (SFF) | 100 % |
| λSU | 2.84 x 10-7(284 FIT) |
| λSD | 0 |
| λDU | 0 |
| λDD | 0 |
| Probability of a hazardous failure on demand (PFDAVG) | 0 (1 year) |
| 0 (5 years) | |
| 0 (10 years) | |
| Diagnostic coverage (DC) | DCS=0 %, DCD=0 % |
Safety data
| Input power Pi | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
| Max. output voltage Uo | 27.7 V |
| Max. output current Io | 101 mA |
| Max. output power Po | 697 mW |
| Group | IIC |
| Max. external inductivity Lo | 4 mH |
| Max. external capacity Co | 0.085 µF |
| Group | IIB |
| Max. external inductivity Lo | 17 mH |
| Max. external capacity Co | 0.663 µF |
| Group | IIA |
| Max. external inductivity Lo | 35 mH |
| Max. external capacity Co | 2.2 µF |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC/IIB/IIA |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1)G Ex nA [ia IIC Ga] IIC T4 Gc X | |
| IECEx | [Ex ia Ga] IIC/IIB/IIA |
| [Ex ia Da] IIIC | |
| Ex nA [ia IIC Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIB | |
| IIA |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |