View larger
MACX MCR-EX-SL-RPSSI-2I-SP 2924236 PHOENIX CONTACT Repeater power supply
MACX MCR-EX-SL-RPSSI-2I-SP
2924236
PHOENIX CONTACT
1 Pcs.
Automation > Isolation amplifier
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact MACX MCR-EX-SL-RPSSI-2I-SP repeater power supply is designed for hazardous area applications, supplying power to 2-wire transmitters while safely transmitting 4-20 mA analog signals across an explosion-proof barrier.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Rated supply voltage DC (EF007078): 19.2 V
- Number of input ranges -60 mV ... +60 mV (EF006927): 0
- Number of input ranges -100 mV ... +100 mV (EF006912): 0
- Number of input ranges -300 mV ... +300 mV (EF006920): 0
- Number of input ranges -500 mV ... +500 mV (EF006926): 0
- Number of input ranges -1 V ... +1 V (EF006906): 0
- Number of input ranges -2 V ... +2 V (EF006913): 0
- Number of input ranges -2.5 V ... +2.5 V (EF006915): 0
- Number of input ranges -5 V ... +5 V (EF006923): 0
- Number of input ranges -10 V ... +10 V (EF006909): 0
- Number of input ranges -20 V ... +20 V (EF006917): 0
- Number of input ranges 0 mV ... 60 mV (EF006905): 0
- Number of input ranges 0 mV ... 100 mV (EF006893): 0
- Number of input ranges 0 mV ... 200 mV (EF006898): 0
- Number of input ranges 0 mV ... 300 mV (EF006901): 0
- Number of input ranges 0 mV ... 500 mV (EF006904): 0
More info
▲Key Commercial Data
| Orderkey | 2924236 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 141 (C-5-2017) |
| GTIN | 4046356463676 |
| Weight per Piece (excluding packing) | 165.000 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 60 °C (Any mounting position) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Permissible humidity (operation) | 10 % ... 95 % (non-condensing) |
| Noise immunity | EN 61000-6-2 When being exposed to interference, there may be minimal deviations. |
Input data
| Signal input | Repeater power supply operation |
|---|---|
| Current input signal | 4 mA ... 20 mA |
| Transmitter supply voltage | > 16 V (20 mA) |
| > 15.1 V (23 mA) | |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
| Polarization and surge protection | Yes |
| Signal input | Signal conditioner operation |
| Current input signal | 0 A ... 20 mA |
| 4 mA ... 20 mA | |
| Voltage drop | approx. 3.9 V (in input isolating amplifier operation) |
| Underload/overload signal range | 0 mA ... 24 mA (Extended transmission range for diagnostics) |
Output data
| Signal output | Repeater power supply operation |
|---|---|
| Current output signal | 4 mA ... 20 mA (Output 1 and output 2 active) |
| Load/output load current output | < 450 Ω (20 mA) |
| < 380 Ω (23 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| ≥ 23 mA (Cable short-circuit in the input) | |
| Signal output | Signal conditioner operation |
| Current output signal | 0 mA ... 20 mA (active) |
| 4 mA ... 20 mA (active) | |
| Load/output load current output | < 450 Ω (20 mA) |
| < 380 Ω (23 mA) | |
| Output ripple | < 20 mVrms |
| Output behavior in the event of an error | 0 mA (Cable break in the input) |
| 0 mA (Cable short-circuit in the input) |
Power supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Max. current consumption | < 75 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.45 W (24 V DC / 20 mA) |
| Nominal supply voltage range | 19.2 V DC ... 30 V DC (24 V DC -20%...+25%) |
| Max. current consumption | < 46 mA (24 V DC / 20 mA) |
| Power dissipation | < 1.1 W (24 V DC/ 20 mA) |
Connection data
| Conductor cross section solid min. | 0.2 mm² |
|---|---|
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
| Connection method | Push-in connection |
General
| No. of channels | 1 |
|---|---|
| Maximum transmission error | < 0.1 % (of final value) |
| Transmission error, typical | < 0.05 % (of final value) |
| Maximum temperature coefficient | < 0.01 %/K |
| Step response (10-90%) | 1.3 ms (for jump 4 mA ... 20 mA, typical) |
| Status display | Green LED (PWR supply voltage) |
| Flammability rating according to UL 94 | V0 |
| Electromagnetic compatibility | Conformance with EMC directive |
| Interference emission | EN 61000-6-4 |
| Housing material | PA 6.6-FR |
| Color | gray |
| Designation | Input/output/power supply |
| Electrical isolation | 300 Vrms(Rated insulation voltage (overvoltage category II; degree of pollution 2, safe isolation as per EN 61010-1)) |
| 2.5 kV (50 Hz, 1 min., test voltage) | |
| Designation | Input/output |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Input/power supply |
| Electrical isolation | 375 V (Peak value in accordance with EN 60079-11) |
| Designation | Output 1/output 2 |
| Electrical isolation | 1.5 kV AC (50 Hz, 1 min., test voltage) |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex nA [ia Ga] IIC T4 Gc | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| SIL | 2 |
Safety data
| Operation | Repeater power supply operation |
|---|---|
| Max. output voltage Uo | 25.2 V |
| Max. output current Io | 93 mA |
| Max. output power Po | 587 mW |
| Group | IIC |
| Max. external inductivity Lo | 2 mH |
| Max. external capacity Co | 107 nF |
| Group | IIB |
| Max. external inductivity Lo | 4 mH |
| Max. external capacity Co | 820 nF |
| Safety-related maximum voltage Um | 253 V AC (125 V DC) |
| Operation | Signal conditioner operation |
| Input voltage Ui | ≤ 30 V |
| Input current Ii | ≤ 150 mA |
| Max. internal inductance Li | negligible |
| Max. internal capacitance Ci | negligible |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC directive |
|---|---|
| Noise emission | EN 61000-6-4 |
| Flammability rating according to UL 94 | V0 |
| Conformance | CE-compliant, additionally EN 61326 |
| ATEX | II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC | |
| II 3 (1) G Ex nA [ia Ga] IIC T4 Gc | |
| IECEx | [Ex ia Ga] IIC |
| [Ex ia Da] IIIC | |
| Ex nA [ia Ga] IIC T4 Gc | |
| UL, USA/Canada | Class I Div 2; IS for Class I, II, III Div 1 |
| DNV GL-Temperature | B |
| DNV GL-Humidity | B |
| DNV GL-Vibration | A |
| DNV GL-EMC | A |
| DNV GL-Enclosure | Required protection according to the Rules shall be provided upon installation on board |
| Group | IIC |
| IIB |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |