View larger
ESSENTIAL-PS/1AC/24DC/120W/EE 2910586 PHOENIX CONTACT Power supply unit
ESSENTIAL-PS/1AC/24DC/120W/EE
2910586
PHOENIX CONTACT
1 Pcs.
Automation > DC-power supply
Power Supplies (PS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed as a Power supply unit, this Phoenix Contact ESSENTIAL-PS/1AC/24DC/120W/EE hardware component converts alternating line voltage into regulated direct current for control panel infrastructure. Power supplies ensure consistent energy delivery to sensors, actuators, and programmable logic controllers.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- 1st secondary output voltage (EF006792): 22 V
- Max. output current 1 (EF008284): 5 A
- Secondary voltage adjustable (EF007002): Yes
- Nominal value output voltage 1 (EF009393): 24 V
- Nominal value output current 1 (EF009396): 5 A
- Short-circuit-proof (EF007332): Yes
- Rated supply voltage AC 50 Hz (EF007076): 85 V
- Rated supply voltage AC 60 Hz (EF007077): 100 V
- Rated supply voltage DC (EF007078): 120 V
- Output voltage stabilized (EF003092): Yes
- Power consumption (EF000346): 249.56 VA
- Power output (EF003034): 120 W
- Stabilized (EF005302): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for rail mounting (EF003972): Yes
- Wall mounting possible (EF003973): No
More info
▲Key Commercial Data
| Orderkey | 2910586 |
|---|---|
| Packing unit | 1 pc |
| GTIN | 4055626464411 |
| Weight per Piece (excluding packing) | 674.800 g |
| Custom tariff number | 85044030 |
| Country of origin | TH (Thailand) |
Dimensions
| Width | 40 mm |
|---|---|
| Height | 123.6 mm |
| Depth | 117.6 mm |
| Installation distances left/right | 10 mm |
| Installation distances top/bottom | 50 mm |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -20 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | ≤ 95 % (at 25 °C, non-condensing) |
| Degree of pollution | 2 |
| Installation height | ≤ 5000 m (> 2000 m, Derating: 10 %/1000 m) |
Input data
| Nominal input voltage range | 100 V AC ... 240 V AC |
|---|---|
| Input voltage range | 85 V AC ... 264 V AC (< 100 V AC derating 1%/V AC) |
| AC frequency range | 47 Hz ... 63 Hz |
| Discharge current to PE | < 0.25 mA (264 V AC) |
| Current consumption | 2.2 A (115 V AC) |
| 1.2 A (230 V AC) | |
| Inrush surge current | typ. 20 A (115 V AC) |
| typ. 40 A (230 V AC) | |
| Mains buffering | typ. 20 ms (115 V AC) |
| typ. 90 ms (230 V AC) | |
| Input fuse | 4 A (slow-blow, internal) |
| Type of protection | Transient surge protection |
| Protective circuit/component | Varistor |
Output data
| Nominal output voltage | 24 V DC ±2 % |
|---|---|
| Setting range of the output voltage (USet) | 22 V DC ... 28 V DC (max. power ≤ 120 W) |
| Nominal output current (IN) | 5 A |
| Derating | -20 °C ... -10 °C (2 % / °C) |
| > 40 °C (1.67 % / °C, 115 V AC) | |
| > 50 °C (2.5 % / °C, 230 V AC) | |
| Max. capacitive load | 8000 μF |
| Active current limitation | 105% - 150% of the max. output power (in the event of short circuit) |
| Residual ripple | < 120 mVPP(-10 °C ... +70 °C) |
| < 240 mVPP(-20 °C ... -10 °C) | |
| Output power | 120 W |
| Typical response time | 200 ms |
| Maximum power dissipation in no-load condition | 0.65 W (115 V AC / 230 V AC) |
| Power loss nominal load max. | 13.3 W (115 V AC / 230 V AC) |
General
| Net weight | 0.54 kg |
|---|---|
| Operating voltage display | Green LED |
| Efficiency | 85 % (115 V AC) |
| 88 % (230 V AC) | |
| Insulation voltage input/output | 3 kV AC |
| Insulation voltage input / PE | 2 kV AC |
| Insulation voltage output / PE | 0.5 kV AC |
| Protection class | I (with PE connection) |
| Degree of protection | IP20 |
| MTBF (Telcordia SR-332) | > 700000 h |
| Assembly instructions | alignable: horizontally 10 mm, vertically 50 mm |
Connection data, input
| Connection method | Screw connection |
|---|---|
| Conductor cross section AWG min. | 18 |
| Conductor cross section AWG max. | 8 |
| Stripping length | 7 mm |
Connection data, output
| Connection method | Screw connection |
|---|---|
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise immunity | EN 61000-6-2 |
| EN 61000-6-1 | |
| Low Voltage Directive | Conformance with Low Voltage Directive 2014/35/EC |
| Standard - Electrical safety | EN 60950-1 |
| Standard – Safety extra-low voltage | EN 60950-1 (SELV) |
| UL approvals | UL/C-UL listed UL 508 |
| Shock | IEC 60068-2-27, 27, half sinusoidal wave: 50g for 11 ms; 3x per direction, 9x overall |
| Vibration (operation) | IEC 60068-2-6, sinusoidal waves: 10 Hz ... 500 Hz, 19,6 m/s² (2g peak), 10 min. per cycle, 60 min. in the X direction |
| Approval - requirement of the semiconductor industry with regard to mains voltage dips | SEMI F47 - 0706 (200 V AC) |