View larger
EMG 22-B1-REL-G 24/TRN24-AND 2298014 PHOENIX CONTACT Relay Module
EMG 22-B1-REL-G 24/TRN24-AND
2298014
PHOENIX CONTACT
10 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact relay module, designated as EMG 22-B1-REL-G 24/TRN24-AND, provides modular signal conversion and switching capabilities for industrial control architecture. System builders incorporate these housed relay units into control panels to facilitate reliable circuit isolation, interface controller outputs with field devices, and maintain clean signal segregation.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage DC (EF003980): 19.2 V
- Voltage type for actuating (EF008242): DC
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 2
- Number of contacts as change-over contact (EF008257): 0
- Type of switch contact (EF003358): Single contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Untreated
- Nominal current (EF000001): 0.021 A
- Degree of protection (IP) (EF005474): IP20
- Width (EF000008): 22.5 mm
- Height (EF000040): 75 mm
More info
▲Key Commercial Data
| Orderkey | 2298014 |
|---|---|
| Packing unit | 10 pc |
| Minimum order quantity | 10 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4017918483807 |
| Weight per Piece (excluding packing) | 85.890 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Coil side
| Nominal input voltage UN | 24 V DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.1 |
| Typical input current at UN | 21 mA |
| Typical response time | 12 ms |
| Typical release time | 7 ms |
| Protective circuit | Reverse polarity protection Polarity protection diode |
| Free-wheeling diode Damping diode | |
| Operating voltage display | LED |
| Power dissipation for nominal condition | 0.5 W |
Contact side
| Contact type | Single contact, 2 N/O contact |
|---|---|
| Type of switch contact | Single contact |
| Contact material | AgNi |
| Maximum switching voltage | 250 V AC |
| Limiting continuous current | 4 A |
| Interrupting rating (ohmic load) max. | 96 W (at 24 V DC) |
| 85 W (at 48 V DC) | |
| 60 W (at 60 V DC) | |
| 44 W (at 110 V DC) | |
| 57 W (at 220 V DC) | |
| 1000 VA (for 250 V AC) |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 12 |
General
| Degree of protection | IP20 |
|---|---|
| Mechanical service life | 3x 107cycles |
| Mounting position | any |
| Net weight (SAP) | 85.89 g |
Standards and Regulations
| Designation | Air clearances and creepage distances, input/output |
|---|---|
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 6 kV (1.2/50 μs) |
| Insulation | Reinforced insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Designation | Air and creepage distances, output/output |
| Standards/regulations | DIN EN 50178: 1998-04 |
| Rated insulation voltage | 260 V |
| Rated surge voltage | 2.2 kV (1.2/50 μs) |
| Insulation | Functional insulation |
| Degree of pollution | 2 |
| Overvoltage category | II |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |