View larger
EMD-BL-PTC-PT 2906253 PHOENIX CONTACT Monitoring relay
EMD-BL-PTC-PT
2906253
PHOENIX CONTACT
1 Pcs.
Automation > Temperature monitoring relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact EMD-BL-PTC-PT monitoring relay serves as a dedicated protection device in electrical control panels, utilized to detect excessive winding temperatures in motors and transformers via connected PTC thermistors. This unit helps prevent insulation breakdown and catastrophic equipment failure by dropping out control circuits during thermal overloads.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- With detachable clamps (EF003340): No
- Error registration possible (EF003423): No
- External reset possible (EF003426): No
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 0
- Number of contacts as change-over contact (EF008257): 1
- Width (EF000008): 17.5 mm
- Height (EF000040): 89.5 mm
- Depth (EF000049): 65.5 mm
More info
▲Key Commercial Data
| Orderkey | 2906253 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 264 (C-5-2017) |
| GTIN | 4055626053745 |
| Weight per Piece (excluding packing) | 74.300 g |
| Custom tariff number | 85364900 |
| Country of origin | AT (Austria) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 70 °C |
Input data
| Maximum temperature coefficient | < 0.05 %/K |
|---|---|
| Function | Winding temperature monitoring |
| Basic accuracy | ± 10 % (of scale end value) |
| Total cold resistance | ≤ 1.5 kΩ |
| Response value | ≥ 3.6 kΩ (Relay drops out) |
| Release value | ≤ 1.6 kΩ (Relay picks up) |
| Short-circuit detection | < 20 Ω |
| Recovery time | > 300 ms |
Contact side
| Contact type | 1 floating PDT |
|---|---|
| Maximum switching voltage | 250 V AC (in acc. with IEC 60947-5-1) |
| Interrupting rating (ohmic load) max. | 1250 VA (5 A / 250 V AC) |
| Output fuse | 5 A (fast-blow) |
General
| Mechanical service life | 15x 106cycles |
|---|---|
| Operating mode | 100% operating factor |
| Mounting position | any |
| Assembly instructions | on standard DIN rail NS 35 in accordance with EN 60715 |
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
| Overvoltage category | III (IEC 60947-5-1) |
| Housing insulation material | Polyamide PA 6.6, self-extinguishing |
| Color | gray |
| Conformance | CE-compliant |
Connection data
| Conductor cross section flexible min. | 0.14 mm² |
|---|---|
| Conductor cross section flexible max. | 2.5 mm² |
| Connection method | Push-in connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2014/30/EU |
|---|---|
| Noise emission | EN 61000-6-3 |
| Noise immunity | EN 61000-6-2 |
| Low Voltage Directive | Conformance with Low Voltage Directive 2006/95/EC (valid until 2016-04-19) / 2014/35/EU (valid from 2016-04-20) |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |