PHOENIX CONTACT ELR W3-24DC/500AC-9I-BR ELR W3- 24DC/500AC- 9I-BR 2900795 PHOENIX CONTACT Hybrid motor starter View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ELR W3- 24DC/500AC- 9I-BR 2900795 PHOENIX CONTACT Hybrid motor starter

ELR W3-24DC/500AC-9I-BR

2900795

PHOENIX CONTACT

1 Pcs.

Hybrid motor starter Hybrid motor starter for reversing motors from 3~AC up to 550V AC, with 24V DC input, 9A output current, adjustable overload disconnect, and limited phase fault detection Hybrid motor starter for reversing 3~ AC motors up to 550 V AC, with 24 V DC input, 9 A output current, adjustable overload shutdown, and limited phase failure detection

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

This Phoenix Contact ELR W3-24DC/500AC-9I-BR hybrid motor starter combines electronic switching technology with robust mechanical design for frequent reversing operations. Hybrid motor starters are utilized in industrial automation to extend contact life and provide reliable motor control without excessive wear.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Hybrid motor starters
  • Product family: CONTACTRON
  • Data management status Article revision: 07
  • Number of phases: 3
  • Motor starter type: Reversing starter
  • Switching frequency: ≤ 2 Hz (Load-dependent)
  • Switching frequency: ≤ 2 Hz (Load-dependent)
  • Maximum power dissipation: 14.6 W
  • Minimum power dissipation: 1.1 W
  • Supply Rated control circuit supply voltage U S: 24 V DC
  • Control supply voltage range: 19.2 V DC ... 30 V DC
  • Rated control supply current I S: 40 mA
  • Protective circuit: Surge protection
  • Insulation characteristics Rated insulation voltage: 500 V
  • Rated surge voltage: 6 kV
  • Overvoltage category: III

More info

▲
Technical data

Product properties
Product typeHybrid motor starters
Product familyCONTACTRON
Data management status
Article revision07

Electrical properties
Number of phases3
Motor starter typeReversing starter
Switching frequency≤ 2 Hz (Load-dependent)
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation14.6 W
Minimum power dissipation1.1 W
Supply
Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS40 mA
Protective circuitSurge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage500 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC

Input data
Control
Input nameControl input right/left
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC5 mA (Input type 1)
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Typical response time< 35 ms
Typical turn-off time< 40 ms
Protective circuitReverse polarity protection

Output data
AC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie9 A (AC-51)
6.5 A (AC-53a)
Mains frequency50/60 Hz
Load current range1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2Class 10A
Cooling time20 min. (for auto reset)
Leakage current0 mA
Protective circuitSurge protection
Acknowledge output
NoteConfirmation 01: floating changeover contact
Contact switching type1 changeover contact
Switching capacity in accordance with IEC 60947-5-13 A (230 V, AC15)
2 A (24 V, DC13)

Connection data
Control circuits
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load circuit
Connection methodScrew connection
Stripping length8 mm
Screw threadM3
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Tightening torque0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.

Signaling
Status displayLED (yellow)
Operating voltage displayGreen LED
Error indicationRed LED

Dimensions
Width22.5 mm
Height107 mm
Depth114 mm

Material specifications
Flammability rating according to UL 94V0 (Housing)

Environmental and real-life conditions
Ambient conditions
Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m

Approvals
UKCA
CertificateUKCA-compliant

Standards and regulations
Standards/regulations
Standards/regulationsIEC 60947-1

Mounting
Mounting typeDIN rail mounting
Assembly notecan be aligned with spacing: see derating
Mounting positionVertical (horizontal DIN rail)

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.