View larger
ELR H5-IS-PT- 24DC/500AC-9-P 2909567 PHOENIX CONTACT Hybrid motor starter as an alternative to a conventiona..
ELR H5-IS-PT-24DC/500AC-9-P
2909567
PHOENIX CONTACT
1 Pcs.
Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Utilizing hybrid switching technology, the Phoenix Contact hybrid motor starter (ELR H5-IS-PT-24DC/500AC-9-P) serves as an alternative to traditional mechanical contactors for frequent motor control cycles. Such components are deployed in machine building and process automation to manage electric motors safely while saving panel space on standard DIN rails.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- With short-circuit release (EF006691): No
- Rated control supply voltage DC (EF003980): 19.2 V
- Voltage type for actuating (EF008242): DC
- Rated operation current Ie (EF001443): 9 A
- Rated operation current at AC-3, 400 V (EF009602): 9 A
- Overload release current setting (EF002336): 1.5 A
- Temperature compensated overload protection (EF009604): No
- Release class (EF006668): CLASS 10
- Type of electrical connection of main circuit (EF006819): Spring clamp connection
- Suitable for rail mounting (EF003972): Yes
- Number of command positions (EF001372): 1
- Suitable for emergency stop (EF001433): Yes
- External reset possible (EF003426): Yes
- Degree of protection (IP) (EF005474): IP20
- Width (EF000008): 22.5 mm
- Height (EF000040): 107.5 mm
More info
▲Key Commercial Data
| Orderkey | 2909567 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 27 (C-5-2019) |
| GTIN | 4055626425498 |
| Weight per Piece (excluding packing) | 320.000 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Maximum altitude | ≤ 2000 m |
| Degree of protection | IP20 |
Device supply
| Rated control circuit supply voltage US | 24 V DC |
|---|---|
| Control supply voltage range | 19.2 V DC ... 30 V DC |
| Rated control supply current IS | 60 mA |
| Type of protection | Surge protection |
| Reverse polarity protection |
Input data
| Input name | Control input: right/left and enable input |
|---|---|
| Note | The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration), unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function. |
| Rated actuating voltage UC | 24 V DC |
| Triggering voltage range | 19.2 V DC ... 30 V DC |
| Rated actuating current IC | 7 mA |
| Switching threshold | 9.6 V (“0” signal) |
| 19.2 V (“1” signal) | |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Typical turn-off time | < 30 ms |
| Type of protection | Reverse polarity protection |
Output data load output
| Output name | AC output |
|---|---|
| Rated operating voltage Ue | 500 V AC |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated operating current Ie | 9 A (AC-51) |
| 7 A (AC-53a) | |
| Mains frequency | 50/60 Hz |
| Load current range | 1.5 A ... 9 A |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10 (≤ 3 A) |
| Cooling time | 20 min. (for auto reset) |
| Leakage current | 0 mA |
| Type of protection | Surge protection |
Output data reply output
| Output name | Acknowledge output |
|---|---|
| Note | Confirmation: floating change-over contact, signal contact |
| Contact type | 1 PDT |
| Switching capacity according to IEC 60947-5-1 | 2 A (24 V, DC13) |
General
| Switching frequency | ≤ 2 Hz (Load-dependent) |
|---|---|
| Mounting position | vertical (horizontal DIN rail, motor output below) |
| Mounting type | DIN rail mounting |
| Assembly instructions | alignable, for spacing see derating |
| Operating mode | 100% operating factor |
| Maximum power dissipation | 7 W |
| Minimum power dissipation | 0.88 W |
| Operating voltage display | Green LED |
| Status display | Yellow LED |
| Indication | Red LED |
Connection data
| Connection name | Control circuits |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Connection data 2
| Connection name | Load circuit |
|---|---|
| Connection method | Push-in connection |
| Stripping length | 10 mm |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Insulation characteristics
| Rated insulation voltage | 550 V |
|---|---|
| Rated surge voltage | 6 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Designation | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit |
| Insulation | Safe isolation (IEC 60947-1) |
| Designation | Isolation characteristics between the control input and control supply voltage to auxiliary circuit |
| Insulation | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
| Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | EN 60947-1 |
| EN 60947-4-2 | |
| EN ISO 13849 | |
| IEC 62061 | |
| IEC 61508 |
Conformance/approvals
| Designation | UL approval |
|---|---|
| Certificate | NLDX.E228652 |
| NRNT.E172140 | |
| Designation | Safety Integrity Level (SIL, IEC 61508) |
| Identification | ≤ 3 |
| Additional text | Safe shutdown |
| Designation | Safety Integrity Level (SIL, IEC 61508) |
| Identification | 2 |
| Additional text | Motor protection |
| Designation | Performance Level (ISO 13849) |
| Identification | ≤ e |
| Additional text | Safe shutdown |
| Designation | Category (ISO 13849) |
| Identification | ≤ 3 |
| Additional text | Safe shutdown |
UL data
| SCCR | 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
|---|---|
| 5 kA (480 V AC (fuse: 20 A RK5 (standard fault))) | |
| FLA | 7.6 A (480 V AC) |
| Group installation | 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded) |
| 30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded) | |
| Category code | NLDX / NRNT |
| Horsepower ratings | 2 hp (120 V AC / 208 V AC) |
| 5 hp (277 V AC / 480 V AC) | |
| Ambient temperature (operation) | -25 °C ... 55 °C |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 4.0 | 27021100 |
|---|---|
| eCl@ss 4.1 | 27021100 |
| eCl@ss 5.0 | 27024000 |
| eCl@ss 5.1 | 27024000 |
| eCl@ss 6.0 | 27024000 |
| eCl@ss 7.0 | 27024002 |
| eCl@ss 8.0 | 27024002 |
| eCl@ss 9.0 | 27370905 |
ETIM
| ETIM 2.0 | EC001037 |
|---|---|
| ETIM 3.0 | EC001037 |
| ETIM 4.0 | EC001037 |
| ETIM 5.0 | EC001037 |
| ETIM 6.0 | EC001037 |
| ETIM 7.0 | EC001037 |