PHOENIX CONTACT ELR H5-IES-PT-24DC/500AC-9-P ELR H5-IES-PT- 24DC/500AC-9-P 2909554 PHOENIX CONTACT Hybrid motor starter as an alternative to a convention.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

ELR H5-IES-PT- 24DC/500AC-9-P 2909554 PHOENIX CONTACT Hybrid motor starter as an alternative to a convention..

ELR H5-IES-PT-24DC/500AC-9-P

2909554

PHOENIX CONTACT

1 Pcs.

Hybrid motor starter as an alternative to a conventional reversing contactor. Reverses 3~ AC motors up to 9 A, offers motor protection, ATEX, and emergency stop up to SIL 3. Possible group shut-down, supply, and relay extension via DIN rail connector. Hybrid motor starter as an alternative to the classic inverter protection circuit. It reverses motors from 3~ AC up to 9 A, offers engine protection, ATEX and emergency stop up to SIL 3. Possibility of group disconnection, power supply and extension of relays by means of rail bus connectors.

Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact ELR H5-IES-PT- 24DC/500AC-9-P 2909554 hybrid motor starter serves as an advanced solid-state switching device designed for frequent and reliable motor control in industrial machinery. These units safely manage operational cycles, providing directional switching and overload protection for three-phase systems without mechanical wear.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Product type: Hybrid motor starters
  • Product family: CONTACTRON
  • Operating mode: 100% operating factor
  • Data management status Article revision: 03
  • Number of phases: 3
  • Motor starter type: Reversing starter
  • Switching frequency: ≤ 2 Hz (Load-dependent)
  • Maximum power dissipation: 7 W
  • Minimum power dissipation: 0.88 W
  • Coordination type: 1
  • Supply Rated control circuit supply voltage U S: 24 V DC
  • Control supply voltage range: 19.2 V DC ... 30 V DC
  • Rated control supply current I S: 60 mA
  • Protective circuit: Surge protection
  • Insulation characteristics Rated insulation voltage: 550 V

More info

▲
Technical data

Product properties
Product typeHybrid motor starters
Product familyCONTACTRON
Operating mode100% operating factor
Data management status
Article revision03

Electrical properties
Number of phases3
Motor starter typeReversing starter
Switching frequency≤ 2 Hz (Load-dependent)
Switching frequency≤ 2 Hz (Load-dependent)
Maximum power dissipation7 W
Minimum power dissipation0.88 W
Coordination type1
Supply
Rated control circuit supply voltage US24 V DC
Control supply voltage range19.2 V DC ... 30 V DC
Rated control supply current IS60 mA
Protective circuitSurge protection
Reverse polarity protection; Parallel polarity protection diode
Insulation characteristics
Rated insulation voltage550 V
Rated surge voltage6 kV
Overvoltage categoryIII
Degree of pollution2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuitSafe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply voltage to auxiliary circuitSafe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Emergency tripping
Operate threshold> 60 A
Response time< 0.5 s

Input data
Control
Input nameControl input: right/left and enable input
NoteThe enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3 ms duration),
unblanking pulses of max. 4 ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC24 V DC
Triggering voltage range19.2 V DC ... 30 V DC
Rated actuating current IC7 mA
Switching threshold9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level< 5 V DC (For EMERGENCY STOP)
Typical turn-off time< 30 ms
Protective circuitReverse polarity protection

Output data
AC output
Rated operating voltage Ue500 V AC
Operating voltage range42 V AC ... 550 V AC
Rated operating current Ie9 A (AC-51)
7 A (AC-53a)
Mains frequency50/60 Hz
Load current range1.5 A ... 9 A
Trigger characteristic in acc. with IEC 60947-4-2Class 10 (≤ 3 A)
Class 10A (> 3 A)
Cooling time20 min. (for auto reset)
Leakage current0 mA
Protective circuitSurge protection; Varistor
Acknowledge output
NoteConfirmation: floating change-over contact, signal contact
Contact switching type1 changeover contact
Switching capacity in accordance with IEC 60947-5-12 A (24 V, DC13)

Connection data
Control circuits
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14
Load circuit
Connection methodPush-in connection
Stripping length10 mm
Conductor cross section rigid0.2 mm² ... 2.5 mm²
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 14

Signaling
Status displayLED (yellow)
Operating voltage displayGreen LED
Error indicationRed LED

Dimensions
Width22.5 mm
Height107.5 mm
Depth114 mm

Material specifications
Flammability rating according to UL 94V0 (Housing)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)-25 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m

Approvals
UKCA
CertificateUKCA-compliant
ATEX
Identification I I (2) G [Ex db] [Ex eb] [Ex pxb]
 II (2) D [Ex tb] [Ex pb]
CertificatePTB 18 ATEX 3004
UL approval
CertificateNLDX.E228652
NRNT.E172140
Safety Integrity Level (SIL, IEC 61508)
Identification≤ 3
NoteSafe shutdown
Safety Integrity Level (SIL, IEC 61508)
Identification2
NoteMotor protection
Performance Level (ISO 13849)
Identification≤ e
NoteSafe shutdown
Category (ISO 13849)
Identification≤ 3
NoteSafe shutdown
UL data
SCCR100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA7.6 A (480 V AC)
Group installation20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category codeNLDX / NRNT
Horsepower ratings2 hp (208 V AC)
2 hp (230 V AC)
2 hp (240 V AC)
5 hp (480 V AC)
Ambient temperature (operation)-25 °C ... 55 °C

Standards and regulations
Standards/regulations
Standards/regulationsEN 60947-1
EN 60947-4-2
EN 50495
EN ISO 13849
IEC 62061
IEC 61508

Mounting
Mounting typeDIN rail mounting
Assembly notealignable, for spacing see derating
Mounting positionvertical (horizontal DIN rail, motor output below)

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.