View larger
ELR 1-SC-230AC/600AC-50 1032927 PHOENIX CONTACT Single-phase solid-state contactor, input voltage: 230 V AC,..
ELR 1-SC-230AC/600AC-50
1032927
PHOENIX CONTACT
1 Pcs.
Automation > Power contactor, AC switching
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact single-phase solid-state contactor designed for rapid, wear-free electronic switching of AC loads in industrial automation. Solid-state switching devices are widely utilized in applications requiring high switching frequencies and silent operation. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1032927
- Packing unit: 1 pc
- Catalog page: Page 49 (C-5-2019)
- GTIN: 4055626538105
- Weight per Piece (excluding packing): 520.000 g
- Custom tariff number: 85362010
- Country of origin: MT (Malta)
- Width: 35 mm
- Height: 110 mm
- Depth: 141 mm
- Ambient temperature (operation): -30 °C ... 70 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Input name: Control input
- Rated actuating voltage U C: 230 V AC
- Triggering voltage range: 24 V AC ... 275 V AC
- Rated actuating current I C: approx. 17 mA
More info
▲Key Commercial Data
| Orderkey | 1032927 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 49 (C-5-2019) |
| GTIN | 4055626538105 |
| Weight per Piece (excluding packing) | 520.000 g |
| Custom tariff number | 85362010 |
| Country of origin | MT (Malta) |
Ambient conditions
| Ambient temperature (operation) | -30 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
Input data
| Input name | Control input |
|---|---|
| Rated actuating voltage UC | 230 V AC |
| Triggering voltage range | 24 V AC ... 275 V AC |
| 24 V DC ... 190 V DC | |
| Rated actuating current IC | approx. 17 mA |
| Switching threshold | ≤ 5 V AC/DC (“0” signal) |
| ≥ 20 V AC/DC (“1” signal) | |
| Transmission frequency | 6 Hz |
| Operating voltage display | Green LED |
Output data load output
| Output name | Load output |
|---|---|
| Operating voltage range | 42 V AC ... 660 V AC |
| Load current range | 500 mA ... 50 A (see to derating) |
| Rated operating current at AC-51 | 50 A |
| Rated operating current at AC-53a | 30 A (TA= 25 °C) |
| 16 A (TA= 40 °C) | |
| Leakage current | < 3 mA (In off state) |
| Residual voltage | < 1 V |
| Surge current | 1900 A (t = 10 ms) |
| Type of protection | Varistor |
General
| Mounting position | Vertical (horizontal DIN rail) |
|---|---|
| Assembly instructions | Can be aligned with ≥ 22.5 mm spacing |
Connection data
| Connection name | Control circuits |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.5 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.5 mm² ... 2.5 mm² |
| Conductor cross section AWG | 18 ... 12 |
Connection data 2
| Connection name | Load circuit |
|---|---|
| Connection method | Screw connection |
| Stripping length | 12 mm |
| Screw thread | M4 |
| Conductor cross section solid | 2.5 mm² ... 6 mm² |
| Conductor cross section flexible | 1 mm² ... 4 mm² |
| Conductor cross section AWG | 14 ... 10 |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | EN 61000-4-2 |
| EN 61000-4-3 | |
| EN 61000-4-4 | |
| EN 61000-4-5 | |
| EN 55011 |