View larger
EEM-MA771 2908286 PHOENIX CONTACT Multi-functional energy measuring device with direct Rogowski connection a..
EEM-MA771
2908286
PHOENIX CONTACT
1 Pcs.
Automation > Multifunction measuring instrument
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact EEM-MA771 is a multi-functional energy measuring device equipped with direct Rogowski connection capabilities for comprehensive electrical network diagnostics. Such power monitoring meters are routinely utilized in industrial plants to track consumption profiles, amperage, voltage, and power quality parameters across complex distribution grids.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Ampere meter (EF006555): Yes
- Reactive power meter (EF006556): Yes
- With rotational speed meter (EF006557): No
- Frequency meter (EF006558): No
- Pulse counter (EF006559): No
- Voltmeter (EF006560): Yes
- Effective power measurement device (EF006561): Yes
More info
▲Key Commercial Data
| Orderkey | 2908286 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 202 (C-5-2019) |
| GTIN | 4055626471969 |
| Weight per Piece (excluding packing) | 540.000 g |
| Custom tariff number | 90303100 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -10 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Maximum altitude | ≤ 2000 m |
| Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
| Degree of protection | IP54 (Display (+ EEM-MA-IP)) |
| IP20 (Housing) |
Input data
| Measuring principle | True r.m.s. value measurement |
|---|---|
| Acquisition of harmonics | up to 63rd harmonic |
| Measured value | AC sine (50/60 Hz) |
| Input name | Voltage measuring input V1, V2, V3 |
| Input voltage range | 35 V AC ... 690 V AC (Phase/Phase) |
| 20 V AC ... 400 V AC (Phase/neutral conductor) | |
| 60 V AC ... 2000000 V AC (primary) | |
| 60 V AC ... 400 V AC (secondary) | |
| Surge voltage capacity | 760 V AC (Phase/Phase) |
| Precision | 0.2 % |
| Input name | Current measurement RC1, RC2, RC3 |
| Input current | 4000 A |
| Response threshold from measuring range nominal value | 5 A |
| Precision | < 1 % |
| 1 % | |
| Reactive power (IEC 62053-23) | Class 2 |
| Description of the input | Digital input in accordance with IEC/EN 61131-2 (type 3) |
| Number | 1 |
| Voltage input signal | 0 V DC ... 30 V DC |
| Current input signal | 2 mA ... 15 mA |
Output data
| Output description | Digital output in accordance with IEC/EN 61131-2 (type 3) |
|---|---|
| Number | 1 |
| Current output signal | ≤ 100 mA |
General
| Display | LCD display, two-color backlit |
|---|---|
| Supply voltage range | 100 V AC ... 400 V AC ( 20 %) |
| 150 V DC ... 250 V DC ( 20 %) | |
| Power consumption | ≤ 4 W |
| Mains type | 3-phase (3 or 4-wire), 2-phase (2-wire), and single-phase (1-wire) |
| Color | gray |
| Conformance | CE-compliant |
| Test voltage | 4 kV AC (50 Hz, 1 min.) |
| Product family | EMpro |
Connection data
| Connection name | Current / voltage / supply |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 6 mm² |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 10 |
| Torque | 0.5 Nm ... 0.6 Nm |
Connection data 2
| Connection name | Digital I/O / communication |
|---|---|
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
| Torque | 0.5 Nm ... 0.6 Nm |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |