View larger
EEM-MA770-EIP 2907953 PHOENIX CONTACT Multifunctional energy measuring device with integrated Modbus/TCP and..
EEM-MA770-EIP
2907953
PHOENIX CONTACT
1 Pcs.
Automation > Multifunction measuring instrument
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact EEM-MA770-EIP is a multifunctional energy measuring device featuring integrated Modbus/TCP communication capabilities for seamless industrial network integration. Energy meters of this grade are deployed in electrical panels to monitor, record, and transmit power consumption and quality parameters. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Product type: Energy measuring device
- Product family: EMpro
- Data management status Article revision: 08
- Maximum power dissipation for nominal condition: 10 VA
- Mains type: 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor)
- Electrical isolation Test voltage: 4 kV AC (50 Hz, 60 s)
- Pollution degree: 2
- Overvoltage category: III (300 V AC)
- Insulation: Reinforced insulation
- Overvoltage category: III (300 V AC)
- Insulation: Reinforced insulation
- Measuring category: III (300 V AC)
- Insulation: Reinforced insulation
- Electrical isolation Digital I/Os Insulation: Functional insulation
- Electrical isolation Communication interface Insulation: Functional insulation
- Supply Supply voltage range: 100 V AC ... 400 V AC (±20 %)
More info
▲| Product type | Energy measuring device |
| Product family | EMpro |
| Data management status | |
| Article revision | 08 |
| Maximum power dissipation for nominal condition | 10 VA |
| Mains type | 3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor) |
| Electrical isolation | |
| Test voltage | 4 kV AC (50 Hz, 60 s) |
| Pollution degree | 2 |
| Electrical isolation Housing against all potentials IEC 61010-1 | |
| Standards/regulations | IEC 61010-1 |
| Overvoltage category | III (300 V AC) |
| II (600 V AC) | |
| Insulation | Reinforced insulation |
| Electrical isolation Supply against all other potentials IEC 61010-1 | |
| Standards/regulations | IEC 61010-1 |
| Overvoltage category | III (300 V AC) |
| II (600 V AC) | |
| Insulation | Reinforced insulation |
| Electrical isolation Voltage measurement input against all other potentials IEC 61010-1 | |
| Standards/regulations | IEC 61010-1 |
| Measuring category | III (300 V AC) |
| II (600 V AC) | |
| Insulation | Reinforced insulation |
| Electrical isolation Current measurement input against all other potentials | |
| Insulation | Functional insulation |
| Electrical isolation Digital I/Os | |
| Insulation | Functional insulation |
| Electrical isolation Communication interface | |
| Insulation | Functional insulation |
| Supply | |
| Supply voltage range | 100 V AC ... 400 V AC (±20 %) |
| 150 V DC ... 250 V DC (±20 %) | |
| Power consumption | ≤ 4 W |
| Nominal frequency | 50 Hz ... 60 Hz (AC sine) |
| General | |
| Measuring principle | True RMS value measurement (TRMS) |
| Measured value | AC sine (50 Hz/60 Hz) |
| Acquisition of harmonics | up to 63rd harmonic |
| Description of the input | Digital input in accordance with IEC/EN 61131-2 (type 3) |
| Number | 1 |
| Voltage input signal | 24 V DC |
| 0 V DC ... 30 V DC | |
| Current input signal | 2 mA ... 15 mA |
| Protection | 250 mA (fast-blow) |
| Measurement: Voltage | |
| Input name | Voltage measuring input V1, V2, V3 |
| Input voltage range direct | 35 V AC ... 690 V AC (Phase/Phase) |
| 20 V AC ... 400 V AC (Phase/neutral conductor) | |
| Input voltage range via external transformers | 60 V AC ... 2000000 V AC (primary) |
| 60 V AC ... 400 V AC (secondary) | |
| Surge voltage capacity | 760 V AC (Phase/Phase) |
| Precision | 0.2 % |
| Power consumption | < 2 VA |
| Measurement: Current | |
| Input name | Current measurement I1, I2, I3 |
| Input current | 1 A (secondary) |
| 5 A (secondary) | |
| Measuring range | 1 A ... 20000 A (primary) |
| Overload capacity | 6 A (Imax) |
| Response threshold from measuring range nominal value | 10 mA (1 A) |
| 50 mA (5 A) | |
| Precision | 0.2 % |
| Current overload | 50 A for 1 s |
| Power consumption | < 0.5 VA |
| Measurement: Power | |
| Precision | 0.5 % |
| Active energy (IEC 62053-22) | Class 0.5 S |
| Reactive power (IEC 62053-23) | Class 2 |
| ANSI C12.20 | Class 0.5 S |
| Output description | Digital output in accordance with IEC/EN 61131-2 (type 3) |
| Number | 1 |
| Current output signal | ≤ 100 mA |
| Voltage output signal | 24 V DC |
| Protection | 250 mA (fast-blow) |
| Current / voltage / supply | |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.2 mm² ... 6 mm² |
| Conductor cross section flexible | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 10 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Digital I/O / communication | |
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross section rigid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 26 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Data: Network interface | |
| Communication protocol | Modbus/TCP |
| REST | |
| Connection method | RJ45 |
| Data: Network interface | |
| Communication protocol | EtherNet/IP™ |
| Connection method | RJ45 |
| Number of connections | 2 |
| Note | DLR ready |
| Width | 96 mm |
| Height | 96 mm |
| Depth | 75 mm |
| Color | gray (RAL 7042) |
| Ambient conditions | |
| Degree of protection (Housing) | IP20 (Housing) |
| Degree of protection (Display) | IP54 (Display (+ EEM-MA-IP)) |
| Ambient temperature (operation) | -10 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Altitude | ≤ 2000 m |
| Max. permissible relative humidity (operation) | ≤ 95 % (non-condensing) |
| CE | |
| Certificate | CE-compliant |
| UKCA | |
| Certificate | UKCA-compliant |
| UL, USA/Canada | |
| Identification | UL/C-UL Listed UL 61010-1 |
| UL data | |
| Operating mode | Indoor use |
| UL data | |
| Operating mode | Indoor use |
| Mounting type | Panel mount |
| Mounting position | Front panel installation, horizontal |