View larger
EEM-EM377 2908590 PHOENIX CONTACT Measuring instrument
EEM-EM377
2908590
PHOENIX CONTACT
1 Pcs.
Automation > Multifunction measuring instrument
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact EEM-EM377 measuring instrument provides precise electrical parameter monitoring for industrial power networks and distribution systems. Energy meters and analyzers are widely deployed to track consumption, voltage levels, and operational performance metrics across electrical installations. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2908590
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- GTIN: 4055626338279
- Weight per Piece (excluding packing): 583.200 g
- Custom tariff number: 85371098
- Country of origin: IT (Italy)
- Width: 72 mm
- Height: 90 mm
- Depth: 67 mm
- Ambient temperature (operation): -25 °C ... 55 °C
- Ambient temperature (storage/transport): -25 °C ... 75 °C
- Max. permissible relative humidity (operation): 80 %
- Designation: Measuring input
- Input voltage range: 3x 184 V ... 288 V (320 V ... 500 V)
- Power consumption: 3.5 VA (1 W)
More info
▲Key Commercial Data
| Orderkey | 2908590 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| GTIN | 4055626338279 |
| Weight per Piece (excluding packing) | 583.200 g |
| Custom tariff number | 85371098 |
| Country of origin | IT (Italy) |
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -25 °C ... 75 °C |
| Max. permissible relative humidity (operation) | 80 % |
Input data
| Designation | Measuring input |
|---|---|
| Input voltage range | 3x 184 V ... 288 V (320 V ... 500 V) |
| Power consumption | 3.5 VA (1 W) |
| Frequency range | 45 Hz ... 65 Hz |
| Energy (EN 50470-3) | Class B |
| Real energy (IEC 62053-21) | Class 1 |
| Reactive power (IEC 62053-23) | Class 2 |
Output data
| Designation | S0 output |
|---|---|
| Output description | Passive opto-isolated |
| Maximum switching voltage | 27 V DC |
| Max. switching current | 27 mA |
General data
| Degree of protection | IP51 (Front) |
|---|---|
| IP20 (Connections) | |
| Protection class | II (EN 50470-1) |
| Electric strength | 6 kV |
| 4 kV (EN 50470-3, 7.2) |
Connection data
| Connection name | Measurement connection |
|---|---|
| Connection method | Screw connection |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Connection name | Other connections |
| Connection method | Screw connection |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |